AERCO BMK 6000 Dual Fuel User Manual

Page 160

Advertising
background image

Benchmark 6000 DF Installation, Operation & Maintenance Manual

APPENDIX A – BOILER MENU DESCRIPTIONS

Page 160 of 219

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0096_0B

03/21/2014

Ph.: 800-526-0288

GF-141

APPENDIX A: BOILER MENU ITEM DESCRIPTIONS – Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU – Cont.

WARMUP

The feature embodied in the next three menu items
eliminates Temperature Overshoots during the
“Warmup” period of a cold ignition cycle on all boilers by
temporarily modifying the PID Gain parameter during
warmup and for a period defined in the Tuning Menu.

Warmup Prop Band

Range = 1-120

Default = 95

Warmup Int Gain

Range = 1-200

Default = 50

Warmup PID Timer

Range = 1-240

Default = 20

Reset Defaults?

Allows Tuning Menu options to be reset to their Factory
Default values.

MENU LEVEL & OPTION

DESCRIPTION

COMBUSTION CAL MENU

*

CAL Voltage 14%

CAL Voltage 30%

CAL Voltage 40%

CAL Voltage 50%

CAL Voltage 70%

CAL Voltage 100%

Displays the default DC drive voltage provided to the
blower at each of the Air/Fuel Valve positions show in
the left-hand column. This drive voltage adjusts the
rotational speed of the blower to maximize combustion
efficiency.

Set Valve Position

Permits selection of the Air/Fuel Valve position (%
open) to be set from 0 to 100%.

Blower Output

Permits the DC drive voltage to the blower to be
monitored.

Set Stby V out

Permits the Standby Voltage to be set from 0 to 4.00
Volts.

Oxygen Level

Permits the combustion oxygen level to be displayed
(0% to 25%).

* NOTE: The Level 2 Password must be entered to view the options in the Combustion Cal

Menu. This Menu is used during the Combustion Calibration procedures described in
Chapter 4 of this Manual.