12 combustion air, 1 combustion from outside the building, 2 combustion air from inside the building – AERCO BMK 6000 Dual Fuel User Manual
Page 33
 
Benchmark 6000 DF Installation, Operation & Maintenance Manual
CHAPTER 2 – INSTALLATION
OMM-0096_0B
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 33 of 219
GF-141
Ph.: 800-526-0288
03/21/2014
For Massachusetts installations, the following companies provide vent systems which conform to 
all applicable requirements for installations within the Commonwealth of Massachusetts. Contact 
information is as follows: 
Selkirk Corporation - Heatfab Division 
130 Industrial Blvd. 
Turners Falls, MA 01376 
Phone: 1-800-772-0739 
Watertown Supply 
33Grove St. 
Watertown, MA 02472 
Phone: (617) 924-2840 
M. A. Peacard 
1250 Massachusetts Ave. 
Boston MA 02125-1689 
Phone: (617) 288-0629 
Glover Sheet Meatal, Inc. 
44 Riverdale Ave. 
Newton, MA 02485 
Phone: (617) 527-8178 
2.12 COMBUSTION AIR
The AERCO Benchmark Boiler Venting and Combustion Air Guide, GF-2050 MUST be 
consulted before any flue or inlet air venting is designed or installed. Air supply is a direct 
requirement of ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These codes should be 
consulted before a permanent design is determined. 
The combustion air must be free of chlorine, halogenated hydrocarbons or other chemicals that 
can become hazardous when used in gas-fired equipment. Common sources of these 
compounds are swimming pools, degreasing compounds, plastic processing, and refrigerants. 
Whenever the environment contains these types of chemicals, combustion air MUST be supplied 
from a clean area outdoors for the protection and longevity of the equipment and warranty 
validation. 
The more common methods of combustion air supply are outlined in the following sections. For 
combustion air supply from ducting, consult the AERCO GF-2050, Gas Fired Venting and 
Combustion Air Guide. 
2.12.1 Combustion From Outside the Building
Air supplied from outside the building must be provided through two permanent openings. For 
each unit these two openings must have a free area of not less than one square inch for each 
4000 BTUs input of the equipment or 1,500 square inches of free area. The free area must take 
into account restrictions such as louvers and bird screens. For Canada installations, refer to the 
requirements specified in CSA B149.1-10, sections 8.4.1 and 8.4.3. 
2.12.2 Combustion Air from Inside the Building
When combustion air is provided from within the building, it must be supplied through two 
permanent openings in an interior wall. Each opening must have a free area of not less than one 
square inch per 1000 BTUH of total input or 6000 square inches of free area. The free area must 
take into account any restrictions, such as louvers. 
NOTE
The source of internal combustion air must be positive or neutral in 
pressure. Negative pressure inside a boiler room may have an adverse 
effect on combustion equipment.