1 required tools & instrumentation, 2 installing gas supply manometer – AERCO BMK 6000 Dual Fuel User Manual

Page 60

Advertising
background image

Benchmark 6000 DF Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

Page 60 of 219

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0096_0B

03/21/2014

Ph.: 800-526-0288

GF-141

4.2.1 Required Tools & Instrumentation

The following tools and instrumentation are necessary to perform combustion calibration of the
unit:

• Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and

Nitrogen Oxide (NOx) resolution to 1PPM.

• 16 inch W.C. manometer or equivalent gauge and plastic tubing.
• 1/4 inch NPT-to-barbed fittings for use with gas supply manometer or gauge.
• Small and large flat blade screwdrivers.
• Tube of silicone adhesive

4.2.2 Installing Gas Supply Manometer

The gas supply manometer (or gauge) is used to monitor the gas pressure on the downstream
side of the SSOV during the Combustion Calibration procedures described in sections 4.4 & 4-5.

The gas supply manometer is installed at the downstream location shown in Figure 4-1.

Figure 4-1: 1/4 Inch Gas Plug Location for Combustion Calibration

TO AIR/FUEL

VALVE

MANUAL SHUT-

OFF VALVE

DOWNSTREAM
SSOV with POC

SWITCH

PROPANE
LOW GAS PRESSURE
SWITCH (8.5” W.C.)

GAS

INLETS

NATURAL GAS

HIGH GAS

PRESSURE

SWITCH

(10.5” W.C.)

1/4" PLUG
(Install Manometer here for PROPANE Combustion Calibration)

NATURAL GAS
LOW GAS
PRESSURE
SWITCH
(8.5” W.C.)

PROPANE
HIGH GAS PRESSURE
SWITCH (6.3” W.C.)

1/4" PLUG
(Install Manometer
here for NATURAL
GAS Combustion
Calibration)

Advertising