Table B-2: Fault Messages – Continued

FAULT MESSAGE

FAULT DESCRIPTION

SSOV FAULT

DURING IGN

The SSOV switch closed or failed to open during ignition.

SSOV FAULT

DURING RUN

The SSOV switch closed for more than 15 seconds during
run.

SSOV RELAY

FAILURE

A failure has been detected in one of the relays that control
the SSOV.

STEPPER MOTOR

FAILURE

The Stepper Motor failed to move the Air/Fuel Valve to the
desired position.

WARNING

EXHAUST TEMP HIGH

The exhaust temperature measured by the exhaust sensor
has exceeded _?_ ºF

WARNING

O2 LEVEL HIGH

The O2 level measured by the O2 sensor has exceeded
_?_ %