8 combustion cal menu, 9 bst (boiler sequencing technology ) menu – AERCO BMK 6000 Dual Fuel User Manual

Page 47

Advertising
background image

Benchmark 6000 DF Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0096_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 47 of 219

GF-141

Ph.: 800-526-0288

03/21/2014

3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu is protected by the level 2 password (6817) which must
be entered to view or change the menu items shown in Table 3-6. These menu items are used to
vary the speed of the unit’s blower motor based on air temperature and air density at prescribed
Air/Fuel Valve positions (% open). This is accomplished by providing a DC drive voltage to the
motor which adjusts the rotational speed of the blower to maximize combustion efficiency and
ensure the unit conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions
specified in Chapter 4. The valve positions (%) and default drive voltages are listed in Table 3-6.

Table 3-6: Combustion Cal Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

CAL Voltage 14%

0.25

10.00

2.20

CAL Voltage 30%

0.25

10.00

2.25

CAL Voltage 40%

0.25

10.00

2.75

CAL Voltage 50%

0.25

10.00

3.85

CAL Voltage 70%

0.25

10.00

6.90

CAL Voltage 100%

0.25

10.00

9.60

SET Valve Position

0.25

10.00

2.20

Blower Output

Monitor Blower Output Voltage

Set Stdby Volt

0.0

4.00 V

0/2.00 V

Oxygen Level

0%

25%

Variable

3.9 BST (BOILER SEQUENCING TECHNOLOGY ) MENU

The BST Menu must be Enabled in order to be displayed and accessed. The BST Enable item is
located at the end of the Configuration Menu.

The Boiler Sequencing Technology (BST) Menu contains all of the items required to Configure,
Operate and Monitor the functionality of the BST System. There are over 50 items in this menu,
and selecting any particular item from the list, for inspection or modification, could be time
consuming. As a result, the BST Menu has been segmented into FIVE logical groups based on
functionality.

The five Item groups are:

1. BST Monitor Items

2. BST SETUP MENU*

3. * OPERATE MENU *

4. *TEMP CTRL MENU*

5. *BST COMM MENU*

These displayed item groups are displayed in UPPER CASE letters, and are bounded by an
asterisk * in order to readily identify them within the item list.

Advertising