6.10 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

Purge Switch Open During Purge

1.

Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set
the valve position between 25% and 30%.

2.

Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it (see
Figure 6-8).

3.

Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-9).

4.

Initiate a unit start sequence.

5.

The unit should begin its start sequence, then shut down and display PRG SWITCH OPEN
DURING PURGE
.

6.

Replace the wire on the Purge Switch and depress the CLEAR button. The unit should
restart.

Figure 6-8: Air/Fuel Valve Cover Location

AIR/FUEL VALVE COVER
(ROTATE CCW TO REMOVE)