PROPANE Gas Combustion Calibration – Continued

15.

Once the oxygen level is within the specified range at 100%, record the O

2

, NOx and

naivety CO readings on the Combustion Calibration Data Sheets provided with the unit.

16.

Lower the valve position to 85 %

using the ▼arrow key.

NOTE

The remaining combustion calibration steps are performed using
the Combustion Cal Menu included in the C-More Control System.
The combustion calibration control functions will be used to adjust
the oxygen level (%) at valve positions of 85%, 65%, 45%, 30%
and 18% as described in the following steps. These steps assume
that the inlet air temperature is within the range of 50°F to 100°F. If
NOx readings exceed the target values shown, increase the O

2

level up to 1% higher than the listed calibration range. Record the
increased O

2

value on the Combustion Calibration sheet.

17.

Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter
password 6817 and then press the ENTER key.

18.

Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu
appears on the display.

19.

Press the ▲ arrow key until SET Valve Position appears on the display.

20.

Press the CHANGE key. SET Valve Position will begin to flash.

21.

Press the ▲ arrow key until the SET Valve Position reads 85%. Press the ENTER key.

22.

Next, press the down

(▼) arrow key until CAL Voltage 85% is displayed.

23.

Press the CHANGE key and observe that CAL Voltage 85% is flashing.

24.

The oxygen level at the 85% valve position should be as shown below. Also, ensure that
the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the following
values:

Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide (NOx)

Carbon Monoxide (CO)

85%

5.5% - ± 0.5%

<200 ppm

<200 ppm

25.

If the oxygen level is not within the specified range, adjust the

level using the ▲ and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.

26.

Once the oxygen level is within the specified range at 85%, press the ENTER key to store
the selected blower output voltage for the 85% valve position. Record all readings on the
Combustion Calibration Sheets provided.

27.

Repeat steps 20 through 26 for valve positions of 65%, 45%, 30% and 18%. The oxygen
(O

2

), nitrogen oxide (NOx) and carbon monoxide (CO) should remain within the same limits

for all valve positions as shown in the following table.