5 USER INTERFACE

5.1

Preliminary notes

The following operating status exist:

-

the “stand-by” status (the device is powered and is off)

-

the “on” status (the device is powered, is on and is in stand-by for the start-up of an operating cycle)

-

the “run” status (the device is powered, is on and an operating cycle is in progress).

Hereon, the term "device switch-on" means the passage from the "stand-by" status to the "on" status. the term "switch-

off" means passage from the "on" status to the "stand-by" status.

If a power cut occurs during the "stand-by" status or during the "on" status, the device will re-propose the same status

when the power supply is restored.

If a power cut occurs during the "run" status, the device will operate as follows when this is restored:

operation after cut-off of the power supply depends on parameter "P6"; if set at 0 the cycle will be interrupted, if set at 1

the cycle will be re-started and if set at 2 the cycle will only be re-started if the the power cut-off supply was less than the

time set by parameter "P5".

5.2

Device commissioning

Operate as follows:

1.

Connect the device power supply. if parameter E9 is set at 1, the device will display the EVCO splash screen for 10

seconds, otherwise it will display a black screen for 10 seconds, after which it will go to the STANDBY status.