13 parameters – EVCO EVFTFT618N7U User Manual

Page 39

Advertising
background image

EVCO S.p.A.

EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

39

of

62

13

Parameters

Par.

Min.

Max.

Unit

Default

Analogue inputs

CA1

-25

25

°C

0

offset cell probe

CA2

-25

25

°C

0

offset evaporator probe

CA3

-25

25

°C

0

offset condenser probe

CA4

-25

25

%r.H.

0

humidity probe offset

P0

0

1

- - - -

1

probe type

0 = PTC

1 = NTC

P2

0

1

- - - -

0

temperature unit of measurement

0 = °C

1 = °F

P3

0

1

- - - -

1

enabling the evaporator probe

0 = disabled

1 = enabled

P4

0

1

- - - -

0

enabling the condenser probe

0 = disabled

1 = enabled

P5

0

60

Min

15

duration of a power supply cut-off during a higher cycle at

which a cycle is interrupted (see also P6)

P6

0

2

- - - -

1

behaviour of the instrument on power supply restore

0 = the cycle will be interrupted

1 = the cycle will be re-started

2 = the cycle will be restarted if the duration of interruption

has been less than parameter P5

P7

0

P8

%r.H.

0

humidity transducer low calibration limit (corresponding to

4mA)

P8

P7

100

%r.H.

100

humidity transducer high calibration limit (corresponding to

a 20mA)

P9

0

250

ds

5

delay displaying temperature variation detected by the

probes

Par.

Min.

Max.

Unit

Default

Cooling regulator

rC0

1

15

°C

2

differential of the parameters rC3, rC4, rC5

rC1

-99

rC2

°C

-20

minimum set-point that can be set for the lock, storage and

manual cooling phases

rC2

rC2

99

°C

20

maximum set-point that can be set for the lock, storage

and manual cooling phases

rC3

0

10

°C

1

cooling neutral area value for the block, storage and

manual cooling phases

rC4

0

10

°C

1

cooling neutral area value for the recovery, proving and

manual heating phases