upper condensing quantity alarms counter as long as the number of
upper condensing quantity alarms enough to give the instrument lock-
ing gets reached (the increasing of the upper condensing quantity
alarms counter gets given also by the upper condensing quantity dig-
ital input activation; see the paragraph Digital inputs on the page 13);
to unlock the instrument turn off and turn on again the instrument.
The parameter AC4 establishes the kind of upper condensing quantity
alarm that the instrument must manage: the upper condensing quan-
tity alarm never gets activated, absolute upper condensing quantity
alarm (in this case the instrument activates the upper condensing quan-
tity alarm when the quantity read by the condensing probe rises above
the alarm setpoint) ...

... or upper condensing quantity alarm relative to the setpoint estab-
lished with the parameter F 1 (in this case the instrument activates the
upper condensing quantity alarm when the quantity read by the con-
densing probe rises above the condenser fans activation setpoint of the
alarm setpoint value).

Speaking of upper condensing quantity alarm

• the parameter i7P establishes the kind of contact of the upper

condensing quantity digital input

• the parameter AC0 establishes the hysteresis (differential) rela-

tive to the alarm setpoint

• the parameter AC1 establishes the alarm setpoint value
• the parameter AC4 establishes the kind of upper condensing

quantity alarm that the instrument must manage

• the parameter AC7 establishes the time that disables an upper

condensing quantity alarm activation from the moment in which
the upper condensing quantity alarm happens

• the parameter ACn establishes the number of upper condens-

ing quantity alarms enough to give the instrument locking

• the parameter A 6 establishes the time that must pass from the

moment of a previous alarms counter increasing in order that
the counter get cleared

the parameters i7P, AC0, AC1, AC4, AC7, ACn and A 6 belong to the
User Menu; see the chapter User Menu on the page 32.

FUNCTIONING
Upper condensing quantity alarm