ciated to the output K7 (1)
Hr 8
----
----
hour
total working hours of the user asso-
ciated to the output K8 (1)
Notes
• the symbol (1) indicates that the parameter is available both to
the first and to the second level
• to clear the users total working hours counter see the para-
graph Users total working hours counter cleaning on the page
11.
Hr 1 total working hours of the user associated to the
output K1
It permits to display the total working hours of the user associated to the
output K1.
Hr 2 total working hours of the user associated to the
output K2
It has the same significance of the parameter Hr 1.
Hr 3 total working hours of the user associated to the
output K3
It has the same significance of the parameter Hr 1.
Hr 4 total working hours of the user associated to the
output K4
It has the same significance of the parameter Hr 1.
Hr 5 total working hours of the user associated to the
output K5
It has the same significance of the parameter Hr 1.
Hr 6 total working hours of the user associated to the
output K6
It has the same significance of the parameter Hr 1.
Hr 7 total working hours of the user associated to the
output K7
It has the same significance of the parameter Hr 1.
Hr 8 total working hours of the user associated to the
output K8
It has the same significance of the parameter Hr 1.
LABEL MIN.
MAX.
U.M.
OPERATOR MENU PASSWORD
OPEr
-999
9999
----
Operator Menu password (2)
Notes
• the symbol (2) indicates that the parameter is available to the
first level only.
OPEr Operator Menu password
It is the password who permits to gain access to the second level of the
Operator Menu.
LABEL MIN.
MAX.
U.M.
USER-RELAY OUTPUT CONFIGURA-
TION
tyP1
undF
CHo
----
user to associate to the output K1
tyP2
undF
CHo
----
user to associate to the output K2
CONFIGURATOR MENU
Configurator Menu configuration parameters
tyP3
undF
CHo
----
user to associate to the output K3
tyP4
undF
CHo
----
user to associate to the output K4
tyP5
undF
CHo
----
user to associate to the output K5
tyP6
undF
CHo
----
user to associate to the output K6
tyP7
undF
CHo
----
user to associate to the output K7
tyP8
undF
CHo
----
user to associate to the output K8
tyP1 user to associate to the output K1
It establishes the user to associate to the output K1, as indicated:
undF
=
no user associated
FAn
=
condenser fans
CP
=
compressor
Cho
=
choking valve.
tyP2 user to associate to the output K2
It has the same significance of the parameter tyP1.
tyP3 user to associate to the output K3
It has the same significance of the parameter tyP1.
tyP4 user to associate to the output K4
It has the same significance of the parameter tyP1.
tyP5 user to associate to the output K5
It has the same significance of the parameter tyP1.
tyP6 user to associate to the output K6
It has the same significance of the parameter tyP1.
tyP7 user to associate to the output K7
It has the same significance of the parameter tyP1.
tyP8 user to associate to the output K8
It has the same significance of the parameter tyP1.
LABEL MIN.
MAX.
U.M.
COMPRESSORS POWER MANAGER
Po 1
1
15
----
power of the compressor associated
to the output K1
Po 2
1
15
----
power of the compressor associated
to the output K2
Po 3
1
15
----
power of the compressor associated
to the output K3
Po 4
1
15
----
power of the compressor associated
to the output K4
Po 5
1
15
----
power of the compressor associated
to the output K5
Po 6
1
15
----
power of the compressor associated
to the output K6
Po 7
1
15
----
power of the compressor associated
to the output K7
Po 8
1
15
----
power of the compressor associated
to the output K8
Po 1 power of the compressor associated to the output
K1
It is significant exclusively if the parameter tyP1 has value CP or Cho, it
establishes a proportion among the compressors powers (for instance