FUNCTIONING

Compressors protection - Users total working hours counter cleaning - Manual power steps loading/unloading

Speaking of compressors protection

• the parameter C 0 establishes the time that disables the com-

pressor activation from the moment in which the instrument
gets supplied

• the parameter C 1 establishes the time that disables the com-

pressor activation from the moment of the previous compres-
sor activation

• the parameter C 2 establishes the time that disables the com-

pressor activation from the moment of the previous compres-
sor deactivation

the parameters C 0, C 1 and C 2 belong to the User Menu; see the
chapter User Menu on the page 32.

USERS TOTAL WORKING HOURS COUNTER CLEANING
To gain access to the users total working hours counter cleaning pro-
cedure:

a) gain access to the second level of the configurator or Opera-

tor Menu (see the chapter Configurator Menu on the page 25
or the chapter Operator Menu on the page 29)

b) push and release over and over the up or the down key as

long as the instrument displays the label of the desired user (for
instance to clear the counter of the total working hours of the
user associated to the output K2 select the label Hr 2)

c) push and release the set key (to the release of the set key the

instrument displays the actual value, for instance 7 and the set
LED flashes to indicate that a configuration parameter modifi-
cation procedure is running; passed four seconds without op-
erated with the keys the instrument automatically turns out
from the configuration parameter modification procedure).

To clear the counter:

d) keep pushed for four seconds at least the down key (passed

four seconds the instrument displays 0)

e) after the modification push and release the set key (to the

release of the set key the instrument displays the label Hr 2
again).

To turn out from the users total working hours counter cleaning proce-
dure:

f) repeat the passage n or n’ of the chapter Configurator Menu

on the page 25.

MANUAL POWER STEPS LOADING/UNLOADING
To gain access to the manual power steps loading/unloading proce-
dure:

a) gain access to the second level of the Operator Menu (see the

chapter Operator Menu on the page 29)

b) push and release over and over the up or the down key as

long as the instrument displays the label of the desired power
step (for instance to load/unload the power step associated to
the output K2 select the label St 2)

c) push and release the set key (to the release of the set key the

instrument displays the actual status, for instance OFF and the
set LED flashes to indicate that a configuration parameter
modification procedure is running; passed four seconds with-
out operated with the keys the instrument automatically turns
out from the configuration parameter modification procedure).