CONFIGURATION PARAMETERS AND DEFAULT VALUES SUMMARIZING TABLE
Operator Menu configuration parameters - User Menu configuration parameters
• the symbol (4) indicates that the unit of measure depends from the parameter /bE (the parameter /bE belongs to the User Menu; see the
chapter User Menu on the page 32): if the condensing probe is a 2 wires 4-20 mA pressure transducer the unit of measure depends from the
parameters /5P, /b6 and /b7 (the parameters /5P, /b6 and /b7 belong to the User Menu; see the chapter User Menu on the page 32), if the
condensing probe is a PTC probe the unit of measure depends from the parameter / t (the parameter / t belongs to the User Menu; see the
chapter User Menu on the page 32)
• the symbol (5) indicates that during the status ON the parameter is available both to the first and to the second level.
USER MENU CONFIGURATION PARAMETERS
LABEL MIN.
MAX.
U.M.
DEF.
USER MENU PASSWORD
PA
-999
9999
----
0
User Menu password (2)
LABEL MIN.
MAX.
U.M.
DEF.
MEASURE INPUTS
/A1
-999
999
(3)
0.00
suction probe calibration (1)
/b1
-999
999
(4)
0.00
condensing probe calibration (1)
/ 2
0
6
----
1
digital filter
/ t
0
1
----
1
temperature unit of measure
/5P
0
3
----
2
pressure decimal point position
/bE
0
2
----
1
kind of condensing probe
/A6
-999
9999
point
-0.50 lower end of scale for 4-20 mA input (it coincides with the minimum calibration value of the suction trans-
ducer)
/A7
-999
9999
point
7.00
upper end of scale for 4-20 mA input (it coincides with the maximum calibration value of the suction
transducer)
/b6
-999
9999
point
0.00
lower end of scale for 4-20 mA input (it coincides with the minimum calibration value of the condensing
transducer)
/b7
-999
9999
point
30.00 upper end of scale for 4-20 mA input (it coincides with the maximum calibration value of the condensing
transducer)
/U
0
1
----
0
kind of analog output (only for devices with analog output in current)
LABEL MIN.
MAX.
U.M.
DEF.
SUCTION PRESSURE REGULATOR
r 0
0.001 999
(3)
0.20
“neutral zone” (1)
r 1
-999
9999
(3)
0.00
minimum working setpoint programmable (1)
r 2
-999
9999
(3)
7.00
maximum working setpoint programmable (1)
r 4
0
100
%
100
percentage of “neutral zone” to apply below the working setpoint
r 5
0
1
----
0
locking of the working setpoint and of the condenser fans activation setpoint modification
r 8
0.10
40.00 min,sec 0.10
loading time (1)
r 9
0.10
40.00 min,sec 0.10
unloading time (1)
r A
0
1
----
1
kind of regulating action (1)
r C
0
1
----
0
kind of choking valve
r E
0
2550
----
100
increase (percentage) of the “neutral zone” (parameter r 0) given by the activation of the input by-pass
regulation
r F
0
4.00
h,min 0.10
maximum time the activation of the input by-pass regulation has effect
LABEL MIN.
MAX.
U.M.
DEF.
COMPRESSORS PROTECTION
C 0
0.00
40.00 min,sec 0.10
disabling time to the compressor activation from the instrument start
C 1
0.00
40.00 min,sec 0.00
disabling time to the compressor activation from the previous activation
C 2
0.00
40.00 min,sec 0.10
disabling time to the compressor activation from the previous deactivation
C 6
0
8
----
0
number of power steps loaded during a suction probe failure alarm
C 7
0
255
hour
0
number of running working hours of the power step enough to request the unloading
C H
0
9999
hour
1000 number of total working hours of the power step enough to signal the request of service (1)