EVCO EC6708 User Manual

Page 43

Advertising
background image

Every Control S.r.l.

Via Mezzaterra 6, 32036 Sedico Belluno ITALY • Phone 0039-0437-852468 (a.r.) • Fax 0039-0437-83648 • [email protected] • www.everycontrol.it

43

CONFIGURATION PARAMETERS AND DEFAULT VALUES SUMMARIZING TABLE

User Menu configuration parameters

LABEL MIN.

MAX.

U.M.

DEF.

CONDENSER FANS REGULATOR

F 0

0.001 255

(4)

2.00

proportional band (1)

F 1

F 6

F 7

(4)

12.00 condenser fans activation setpoint (1)

F 6

-999

9999

(4)

0.00

minimum condenser fans activation setpoint programmable (1)

F 7

-999

9999

(4)

30.00 maximum condenser fans activation setpoint programmable (1)

F A

0

1

----

0

condenser fans functioning

F d

0

1

----

0

method used to compute which condenser fans activate/deactivate

F H

0

9999

hour

9999

number of total working hours of the condenser fans enough to signal the request of service (1)

LABEL MIN.

MAX.

U.M.

DEF.

DIGITAL INPUTS

i1P

0

1

----

0

kind of contact of the user compressor associated to the output K1 ... 8 locking digital inputs

i2P

0

1

----

0

kind of contact of the user condenser fans associated to the output K1 ... 8 locking digital inputs

i4P

0

1

----

0

input configuration (freon level or by-pass regulation)

i5P

0

1

----

0

kind of contact of the input freon level/by-pass regulation

i6P

0

1

----

0

kind of contact of the condenser fans safety digital input

i7P

0

1

----

0

kind of contact of the upper condensing quantity digital input

i8P

0

1

----

0

kind of contact of the lower pressure digital input

LABEL MIN.

MAX.

U.M.

DEF.

LOWER PRESSURE ALARM

AA0

0.001 255

(3)

0.01

hysteresis (differential)

AA1

-999

9999

(3)

0.00

alarm setpoint

AA4

0

2

----

0

kind of alarm

AA7

0.00

4.15

min,sec 0.00

disabling time to the lower pressure alarm activation

AAn

0

15

----

0

number of lower pressure alarms enough to give the instrument locking

LABEL MIN.

MAX.

U.M.

DEF.

UPPER PRESSURE ALARM

Ab0

0.001 255

(3)

0.01

hysteresis (differential)

Ab1

-999

9999

(3)

0.00

alarm setpoint

Ab4

0

2

----

0

kind of alarm

Ab7

0.00

4.15

min,sec 0.00

disabling time to the upper pressure alarm activation

Abn

0

15

----

0

number of upper pressure alarms enough to give the instrument locking

LABEL MIN.

MAX.

U.M.

DEF.

UPPER CONDENSING QUANTITY ALARM

AC0

0.001 255

(3)

0.01

hysteresis (differential)

AC1

-999

9999

(3)

0.00

alarm setpoint

AC4

0

2

----

0

kind of alarm

AC7

0.00

4.15

min,sec 0.00

disabling time to the upper condensing quantity alarm activation

ACn

0

15

----

0

number of upper condensing quantity alarms enough to give the instrument locking

LABEL MIN.

MAX.

U.M.

DEF.

PRESSURE ALARMS DISABLING

A 3

0.00

4.15

h,min 0.00

disabling time to the upper pressure alarm activation from the instrument start

A 6

0.00

4.15

h,min 0.00

time required to clear the pressure alarms counters

LABEL MIN.

MAX.

U.M.

DEF.

CONNECTION IN A SERIAL NETWORK WITH EVCOBUS PROTOCOL COMMUNICATION

L 1

1

15

----

1

instrument address

L 2

0

7

----

0

instrument group

L 4

0

3

----

1

baud rate

LABEL MIN.

MAX.

U.M.

DEF.

OPERATOR MENU PASSWORD VALUE