EVCO EC6708 User Manual

Page 36

Advertising
background image

Every Control S.r.l.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY • Phone 0039-0437-852468 (a.r.) • Fax 0039-0437-83648 • [email protected] • www.everycontrol.it

36

USER MENU
User Menu configuration parameters

the unit of measure depends from the parameters /5P, /b6
and /b7 (the parameters /5P, /b6 and /b7 belong to the User
Menu; see the chapter User Menu on the page 32), if the
condensing probe is a PTC probe the unit of measure depends
from the parameter / t (the parameter / t belongs to the User
Menu; see the chapter User Menu on the page 32).

F 0

proportional band

It is significant exclusively if the parameter /bE has value 1 or 2 and if
the parameter F A has value 0, it establishes the proportional band
width.
For further informations about the parameter F 0 meaning see the
paragraph Condensing quantity regulation on the page 12.
F 1

condenser fans activation setpoint

It has the same significance of the parameter F 1 of the Operator
Menu; see the chapter Operator Menu on the page 29.
F 6

minimum condenser fans activation setpoint pro-
grammable

It is significant exclusively if the parameter /bE has value 1 or 2 and if
the parameter F A has value 0, it establishes the minimum condenser
fans activation setpoint programmable; the instrument automatically
verifies if the value established with the parameter F 6 is below the
maximum condenser fans activation setpoint programmable estab-
lished with the parameter F 7.
F 7

maximum condenser fans activation setpoint pro-
grammable

It is significant exclusively if the parameter /bE has value 1 or 2 and if
the parameter F A has value 0, it establishes the maximum condenser
fans activation setpoint programmable; the instrument automatically
verifies if the value established with the parameter F 7 is above the
minimum condenser fans activation setpoint programmable established
with the parameter F 6.
F A

condenser fans functioning

It establishes the condenser fans functioning that the instrument must
manage, as indicated:
0

=

the condenser fans functioning is function of the quan-
tity read by the condensing probe (the instrument
automatically divides the proportional band established
with the parameter F 0 in equal fractions according
with the number of relay outputs associated to the
condenser fans, it activates the condenser fans with
sequence every time the quantity read by the con-
densing probe rises above the setpoint established
with the parameter F 1 of a fraction of proportional
band and it deactivates them with sequence when
the quantity read by the condensing probe falls below
the value to which the activation happened of a frac-
tion of proportional band)

1

=

the condenser fans functioning is function of the power
steps loading/unloading (a power step loading/un-

loading gives the automatic activation/deactivation of
a condenser fans).

For further informations about the parameter F A meaning see the
paragraph Condensing quantity regulation on the page 12.
F d

method used to compute which condenser fans
activate/deactivate

It establishes the method used by the instrument to compute which
condenser fans activate/deactivate, as indicated:
0

=

the instrument activates the condenser fans with fixed
sequence and it deactivates them with the reversal
method (for instance if the users associated to the
outputs K5, K6, K7 and K8 are condenser fans, the
instrument activates them beginning from that associ-
ated to the output K5 and it deactivates them with the
reversal method)

1

=

the instrument activates the condenser fans balancing
the total working hours and it deactivates them with
the reversal method (for instance the instrument acti-
vates the condenser fans with sequence beginning
from that with the lower number of total working
hours and it deactivates them with the reversal
method).

F H

number of total working hours of the condenser
fans enough to signal the request of service

It establishes the number of total working hours of a condenser fans
enough to signal the request of service (see the paragraph Alarms on
the page 46).

LABEL MIN.

MAX.

U.M.

DIGITAL INPUTS

i1P

0

1

----

kind of contact of the user compres-
sor associated to the output K1 ... 8
locking digital inputs

i2P

0

1

----

kind of contact of the user condenser
fans associated to the output K1 ... 8
locking digital inputs

i4P

0

1

----

input configuration (freon level or by-
pass regulation)

i5P

0

1

----

kind of contact of the input freon level/
by-pass regulation

i6P

0

1

----

kind of contact of the condenser fans
safety digital input

i7P

0

1

----

kind of contact of the upper condens-
ing quantity digital input

i8P

0

1

----

kind of contact of the lower pressure
digital input

i1P

kind of contact of the user compressor associated
to the output K1 ... 8 locking digital inputs

It is significant exclusively if the parameter tyP1 ... 8 has value CP, it
establishes the kind of contact of the user compressor associated to the

Advertising