BEFORE THE USE
Settings to execute before the use

SETTINGS TO EXECUTE BEFORE THE USE
To adjust the instrument to the power plant characteristics, it is impor-
tant to execute some settings before the use:

a) after supplied the instrument verify if the instrument is in the

status STAND-BY (during the status STAND-BY the display and
the LED are turned off, except the ON STAND-BY LED)

b) if the instrument is in the status ON keep pushed for two

seconds at least the ON STAND-BY key (passed two seconds
the instrument moves to the status STAND-BY)

c) set the working setpoint value (the working setpoint estab-

lishes the suction pressure associated to the compressors; see
the chapter Working setpoint on the page 24)

d) set the parameters tyP1 ... 8 value (the parameters tyP1 ... 8

establish the users to associate to the outputs K1 ... 8)

e) set the parameters Po 1 ... 8 value (the parameters Po 1 ... 8

establish a proportion among the compressors powers)

the parameters tyP1 ... 8 and Po 1 ... 8 belong to the Configurator
Menu; see the chapter Configurator Menu on the page 25

f) set the parameters /A6 and /A7 value (the parameters /A6 and

/A7 establish the lower and the upper end of scale for 4-20 mA
input of the suction transducer)

g) set the parameter /5P value (the parameter /5P establishes

where to display the decimal point)

h) set the parameter /bE value (the parameter /bE establishes

the kind of condensing probe that the instrument must recog-
nize)

i)

if the condensing probe is a 2 wires 4-20 mA pressure trans-
ducer set the parameters /b6 and /b7 value (the parameters

/b6 and /b7 establish the lower and the upper end of scale for
4-20 mA input of the condensing transducer)

j) if the condensing probe is a PTC probe set the parameter / t

value (the parameter / t establishes the unit of measure with
which the temperature gets displayed)

k) set the parameter r 0 value (the parameter r 0 establishes the

“neutral zone” value of the suction pressure regulator)

l)

if a compressor at least is choked set the parameter r C value
(the parameter r C establishes the kind of choking valve that
the instrument must manage)

m) set the parameter F 0 value (the parameter F 0 establishes the

proportional band width of the condenser fans regulator)

n) set the parameter F 1 value (the parameter F 1 establishes the

condensing quantity value to which the instrument activates
the condenser fans)

o) set the parameter F A value (the parameter F A establishes the

condenser fans functioning)

the parameters /A6, /A7, /5P, /bE, /b6, /b7, / t, r 0, r C, F 0, F 1 and
F A belong to the User Menu; see the chapter User Menu on the page
32.