WORKING SETPOINT
Working setpoint setting (working suction pressure) - Working setpoint

WORKING SETPOINT SETTING (WORKING SUCTION PRES-
SURE)
To modify the working setpoint value:

a) push and release the set key (to the release of the set key the

instrument displays the actual value, for instance 0.00 bar, the
compressors/choking valves and condenser fans associated to
the outputs K1 ... 8 LED turning on to indicate the actual user-
relay output configuration and the set LED flashes to indicate
that a working setpoint setting procedure is running; passed
four seconds without operated with the keys the instrument
automatically turns out from the working setpoint setting pro-
cedure)

b) push and release over and over the up or the down key within

four seconds as long as the instrument displays the desired
value, for instance 1.00 bar (keeping pushed the up or the
down key the value gets increased or decreased more quickly)

c) after the modification push and release the set key (to the

release of the set key the instrument turns out from the work-
ing setpoint setting procedure).

Additional informations
• during a corrupted memory data alarm the access to the

working setpoint setting procedure is refused (see the para-
graph Alarms on the page 46)

• the working setpoint value gets stored in a non volatile memory

even if a lack of power supply happens.

WORKING SETPOINT

LABEL MIN.

MAX.

U.M.

WORKING SETPOINT

r 1

r 2

(3)

working setpoint

Notes
• the parameters r 1 and r 2 belong to the User Menu; see the

chapter User Menu on the page 32

• the symbol (3) indicates that the unit of measure depends from

the parameter /5P and from the parameters /A6 and /A7 (the
parameters /5P, /A6 and /A7 belong to the User Menu; see the
chapter User Menu on the page 32).

working setpoint

It establishes the suction pressure associated to the compressors.
For further informations about the working setpoint meaning see the
paragraph Suction pressure regulation on the page 9.