EVCO EC6708 User Manual

Page 35

Advertising
background image

Every Control S.r.l.

Via Mezzaterra 6, 32036 Sedico Belluno ITALY • Phone 0039-0437-852468 (a.r.) • Fax 0039-0437-83648 • [email protected] • www.everycontrol.it

35

the previous activation

It establishes the time that disables the compressor activation from the
moment of the previous compressor activation.
For further informations about the parameter C 1 meaning see the
paragraph Compressors protection on the page 10.
C 2

disabling time to the compressor activation from
the previous deactivation

It establishes the time that disables the compressor activation from the
moment of the previous compressor deactivation.
For further informations about the parameter C 2 meaning see the
paragraph Compressors protection on the page 10.
C 6

number of power steps loaded during a suction
probe failure alarm

It establishes the number of power steps loaded during a suction probe
failure alarm, except what established with the parameters r 8 and r 9
and except what established with the disabling times to the compres-
sors activation (see the paragraph Alarms on the page 46).
C 7

number of running working hours of the power
step enough to request the unloading

It establishes the number of running working hours of a power step
enough to request the power step unloading (for instance, when the
conditions will permit it, the instrument will unload at first the power
step who will have the number of running working hours established
with the parameter C 7).
C H

number of total working hours of the power step
enough to signal the request of service

It establishes the number of total working hours of a power step enough
to signal the request of service (see the paragraph Alarms on the page
46).

LABEL MIN.

MAX.

U.M.

CONDENSER FANS REGULATOR

F 0

0.001 255

(4)

proportional band (1)

F 1

F 6

F 7

(4)

condenser fans activation setpoint (1)

F 6

-999

9999

(4)

minimum condenser fans activation
setpoint programmable (1)

F 7

-999

9999

(4)

maximum condenser fans activation
setpoint programmable (1)

F A

0

1

----

condenser fans functioning

F d

0

1

----

method used to compute which con-
denser fans activate/deactivate

F H

0

9999

hour

number of total working hours of the
condenser fans enough to signal the
request of service (1)

Notes
• the symbol (1) indicates that the parameter is available both to

the first and to the second level

• the symbol (4) indicates that the unit of measure depends from

the parameter /bE (the parameter /bE belongs to the User
Menu; see the chapter User Menu on the page 32): if the
condensing probe is a 2 wires 4-20 mA pressure transducer

USER MENU

User Menu configuration parameters

power steps).

For further informations about the parameter r A meaning see the
paragraph Suction pressure regulation on the page 9.
r C

kind of choking valve

It establishes the kind of choking valve that the instrument must man-
age, as indicated:
0

=

NC choking valve

1

=

NO choking valve.

For further informations about the parameter r C meaning see the
paragraph Suction pressure regulation on the page 9.
r E

increase (percentage) of the “neutral zone”
(parameter r 0) given by the activation of the
input by-pass regulation

It sets the increase (percentage) of the “neutral zone” (parameter r 0)
when one activates the input for by-pass regulation (the instrument will
automatically increase the “neutral zone” applied over the working
setpoint; for example, set 100 % to double the value).
r F

maximum time the activation of the input by-pass
regulation has effect

It sets the maximum time the activation of the input by-pass regulation
has effect; as soon as this time passes, the instrument will automatically
recover the normal operation, even is the input is activated; if the
parameter has value 0, the instrument will consider 99 min).

LABEL MIN.

MAX.

U.M.

COMPRESSORS PROTECTION

C 0

0.00

40.00 min,sec disabling time to the compressor acti-

vation from the instrument start

C 1

0.00

40.00 min,sec disabling time to the compressor acti-

vation from the previous activation

C 2

0.00

40.00 min,sec disabling time to the compressor de-

activation from the previous activation

C 6

0

8

----

number of power steps loaded dur-
ing a suction probe failure alarm

C 7

0

255

hour

number of running working hours of
the power step enough to request
the unloading

C H

0

9999

hour

number of total working hours of the
power step enough to signal the re-
quest of service (1)

Notes
• the symbol (1) indicates that the parameter is available both to

the first and to the second level.

C 0

disabling time to the compressor activation from
the instrument start

It establishes the time that disables the compressor activation from the
moment in which the instrument gets supplied.
For further informations about the parameter C 0 meaning see the
paragraph Compressors protection on the page 10.
C 1

disabling time to the compressor activation from