4

Monitor xL™ Advanced Installation Guide

21-3602E rev1.5

S00104 Keypad Selections
(left to right on keypad screen) Example:



Default Name

Selections

Description

00

Confirmed Alarm Time
Out

Time table codes.

(UK ACPO = 18)

0

Maximum Number of
Alarms per Point
Arming State

0 = All, 1 = 1, 2 = 2, 3 = 3 Primarily for
European Users.

(UK ACPO = 3)

0

Menu Navigation

0 = Standard, 1 = Ok-SOFT-3, 2 = Ok-
SOFT-1, 3 = future.

0

LCD Menu Style

0 = Standard, 1 = Ok-SOFT-3, 2 = Ok-
SOFT-1, 3 = future.

0

Unconfirmed Reset
Mode

0 = None, 1 = Follow Confirm Alarm, 2 =
Include Master, 3 = future.

(no)

Confirm Reset Service

(yes)

(no)

(UK ACPO = yes)

(no)

Confirm Reset Master

(yes)

(no)

(no)

Confirm Reset
Challenged PIN.

(yes)

(no)

(no)

Confirm Reset using
Remote

(yes)

(no)


S001
05 Keypad Selections (left to right on keypad screen)
Default Name

Selections

Description

01100

AC
Reference
Voltage

Main panel electrical mains operation.
E.g. 01100 = 110.0 Decivolts

(UK ACPO = 02200)

070

Battery
Size

Amp hours X 10
E.g. display as 7.0

(UK ACPO = 17.0)

0

AC Sync

0=60 Hz, 1=50 Hz, 2=No sync required,
3=DC supply

Synchronization with AC line to maximize internal clock
accuracy. With an unstable AC source, select "2: AC-
No Sync" ('AC failure' will be reported if the frequency
drops below 12.5 Hz). With a DC source, be sure to
disable E003 (AC Trouble) under "Equipment
Settings".
DC supply option will not detect power failure condition
and will not have a time base sync

(UK ACPO = 1)

0

AC
Brownout
Mode

0=None, 1=Local alarm, 2=Alarm+report,
3=Report only


S001
06 Keypad Selections (left to right on keypad screen)
Default Name

Selections

Description

001

VBUS Panel Output Base

See: Main Panel Output
Examples:
next

What number the outputs that will be used on
the main controller’s VBUS connection will
start at.

001

Paging Output Base

See: Main Panel Output
Examples:
next

What number the outputs that will be used on
the paging system will start at.

Also see S005:08, 09

001

Output Base for:

World Wide Modem with 8 output STU
REDCARE interface or 8 output STU
REDCARE interface

STU = Subscriber Terminal Unit

See: Main Panel Output
Examples:
next

What number the outputs that will be used
with the main control board output plug in
boards will start at.

(UK ACPO = 003)

00

·

0

·

0

·

0

·

0

·

·

Save S001

04