Monitor xL™ Advanced Installation Guide
21-3602E rev1.5
R00108 Keypad Selections
(left to right on keypad screen) Example:
Default Name
Selections
Description
06
Door Held Open Time
00-31 (Delay Table)
06 =15 Sec
How long the door can be held open after
access is granted without causing an alarm.
10
Challenged Door Held
Open Time
00-31 (Delay Table)
10=1 Min
How long the door can be held open without
causing an alarm after a physically-
challenged user enters. Whether or not the
'Challenged' door held open time applies is
based on the 'Challenged' setting for the
user. For details, refer to U00102
(“Physically Challenged“ Setting).
14
Auxiliary Relay Output
Time
00-31 (Delay Table)
14=5Mins
How long the door can be held open after
access is granted without causing an alarm.
0
Auxiliary Input Mode
0=None, 1=Mag Lock Bond Sense,
2=Challenged RTE,
3= (future) Panel Control
This specifies how the auxiliary input on this
door-controller module is to be used.
0
Auxiliary Relay Output
Mode
0=None, 1=Door Held Open / Door
Forced **, 2=Door Opener *,
3=future
Operation of the alarm relay on the door-
controller module
(no) Reader Tamper
Required
(yes)
□
(no)
Whether or not this reader tamper input is to
be monitored.
(no)
Reader tamper as
Panel Input
(yes)
□
(no)
* Will fire output in this mode when auxiliary input mode is set to challenged RTE and auxiliary input is activated.
** Will fire output in this mode when the condition specified in Door Processing Mode is detected.
R00109 Keypad Selections (left to right on keypad screen)
Default Name
Selections
Description
00
Door Forced / Held
Time
00-31, Global Delay Table
0
Door Circuit
0=NC
1=NC/EOL
2=NO/EOL & Form-C SEOL
3=Form-C DEOL
The type of circuit/wiring being used with
the door contact.
0
RTE Circuit
(request to exit)
0=NC
1=NC/EOL
2=NO/EOL & Form-C SEOL
3=Form-C DEOL
The type of circuit/wiring being used with
the RTE input.
0
Reader Tamper Circuit 0=NC
1=NC/EOL
2=NO/EOL & Form-C SEOL
3=Form-C DEOL
The type of circuit/wiring being used with
the reader tamper.
0
Auxiliary Circuit
0=NC
1=NC/EOL
2=NO/EOL & Form-C SEOL
3=Form-C DEOL
The type of circuit/wiring being used with
the aux. input.
(no)
Do Not Lock on Door
Closure
(yes)
□
(no)
(no)
Insertion Reader
(yes)
□
(no)
(no)
Force Door Buzzer
stops on Closure
(yes)
□
(no)
Legend:
0 = NC: Circuit type 0 (Normally Closed), 1 = NC/EOL: Circuit type 1 (Normally Close with EOL),
2 = NO/EOL:
Circuit type 2 (Normally Open with EOL and Form C Single EOL), 3 = Circuit type 3 (Form C Dual EOL).
06
·
10
·
14
·
0
·
0
·
····
Save R001
08