Carrier 19XL User Manual

Page 22

Advertising
background image

Table 2 — LID Screens (cont)

EXAMPLE 2 — STATUS02 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press STATUS .

3. Scroll down to highlight STATUS02.

4. Press SELECT .

DESCRIPTION

POINT TYPE

UNITS

REFERENCE POINT NAME

(ALARM HISTORY)

INPUT

OUTPUT

Hot Gas Bypass Relay

X

OFF/ON

HGBR

*Chilled Water Pump

X

OFF/ON

CHWP

Chilled Water Flow

X

NO/YES

EVFL

*Condenser Water Pump

X

OFF/ON

CDP

Condenser Water Flow

X

NO/YES

CDFL

Compressor Start Relay

X

OFF/ON

CMPR

Compressor Start Contact

X

OPEN/CLOSED

1CR

AUX

Compressor Run Contact

X

OPEN/CLOSED

RUN

AUX

Starter Fault Contact

X

OPEN/CLOSED

STR

FLT

Pressure Trip Contact

X

OPEN/CLOSED

PRS

TRIP

Single Cycle Dropout

X

NORMAL/ALARM

V1

CYCLE

Oil Pump Relay

X

OFF/ON

OILR

Oil Heater Relay

X

OFF/ON

OILH

Motor Cooling Relay

X

OFF/ON

MTRC

*Tower Fan Relay

X

OFF/ON

TFR

Compr. Shunt Trip Relay

X

OFF/ON

TRIPR

Alarm Relay

X

NORMAL/ALARM

ALM

Spare Prot Limit Input

X

ALARM/NORMAL

SPR

PL

NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations from the LID only.

EXAMPLE 3 — STATUS03 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press STATUS .

3. Scroll down to highlight STATUS03.

4. Press SELECT .

DESCRIPTION

RANGE

UNITS

REFERENCE POINT NAME

(ALARM HISTORY)

OPTIONS BOARD 1
*Demand Limit 4-20 mA

4-20

mA

DEM

OPT

*Temp Reset 4-20 mA

4-20

mA

RES

OPT

*Common CHWS Sensor

–40-245 (–40-118)

DEG F (DEG C)

CHWS

*Common CHWR Sensor

–40-245 (–40-118)

DEG F (DEG C)

CHWR

*Remote Reset Sensor

–40-245 (–40-118)

DEG F (DEG C)

R

RESET

*Temp Sensor — Spare 1

–40-245 (–40-118)

DEG F (DEG C)

SPARE1

*Temp Sensor — Spare 2

–40-245 (–40-118)

DEG F (DEG C)

SPARE2

*Temp Sensor — Spare 3

–40-245 (–40-118)

DEG F (DEG C)

SPARE3

OPTIONS BOARD 2
*4-20 mA — Spare 1

4-20

mA

SPARE1

M

*4-20 mA — Spare 2

4-20

mA

SPARE2

M

*Temp Sensor — Spare 4

–40-245 (–40-118)

DEG F (DEG C)

SPARE4

*Temp Sensor — Spare 5

–40-245 (–40-118)

DEG F (DEG C)

SPARE5

*Temp Sensor — Spare 6

–40-245 (–40-118)

DEG F (DEG C)

SPARE6

*Temp Sensor — Spare 7

–40-245 (–40-118)

DEG F (DEG C)

SPARE7

*Temp Sensor — Spare 8

–40-245 (–40-118)

DEG F (DEG C)

SPARE8

*Temp Sensor — Spare 9

–40-245 (–40-118)

DEG F (DEG C)

SPARE9

NOTE: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*) support write operations for BEST
programming language, data transfer, and overriding.

EXAMPLE 4 — SETPOINT DISPLAY SCREEN

To access this display from the LID default screen:

1. Press

MENU

.

2. Press SETPOINT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

Base Demand Limit

40-100

%

DLM

100

LCW Setpoint

20-120 (–6.7-48.9)

DEG F (DEG C)

lcw

sp

50.0 (10.0)

ECW Setpoint

20-120 (–6.7-48.9)

DEG F (DEG C)

ecw

sp

60.0 (15.6)

ICE BUILD Setpoint

20- 60 (–6.7-15.6)

DEG F (DEG C)

ice

sp

40.0 ( 4.4)

22