Table 3 — Protective Safety Limits and Control Settings

MONITORED PARAMETER

LIMIT

APPLICABLE COMMENTS

TEMPERATURE SENSORS
OUT OF RANGE

–40 to 245 F (–40 to 118.3 C)

Must be outside range for 2 seconds

PRESSURE TRANSDUCERS
OUT OF RANGE

0.08 to 0.98 Voltage Ratio

Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage
Reference

COMPRESSOR DISCHARGE
TEMPERATURE

Ͼ

220 F (104.4 C)

Preset, alert setting configurable

MOTOR WINDING TEMPERATURE

Ͼ

220 F (104.4 C)

Preset, alert setting configurable

BEARING TEMPERATURE

Ͼ

185 F (85 C)

Preset, alert setting configurable

EVAPORATOR REFRIGERANT
TEMPERATURE

Ͻ

33 F (for water chilling) (0.6° C)

Preset, configure chilled medium for
water (Service1 table)

Ͻ

Brine Refrigerant Trippoint (set point adjustable

from 0 to 40 F [–18 to 4 C] for brine chilling)

Configure chilled medium for brine
(Service1 table). Adjust brine refrigerant
trippoint for proper cutout

TRANSDUCER VOLTAGE

Ͻ

4.5 vdc

Ͼ

5.5 vdc

Preset

CONDENSER PRESSURE — SWITCH

Ͼ

263 ± 7 psig (1813 ± 48 kPa),

reset at 180 ± 10 (1241 ± 69 kPa)

Preset

— CONTROL

Ͼ

260 psig (1793 kPa) for HCFC-22;

215 psig (1482 kPa) for HFC-134a

Preset

OIL PRESSURE — SWITCH

Cutout

Ͻ

11 psid (76 kPad) ± 1.5 psid (10.3 kPad)

Cut-in

Ͼ

16.5 psid (114 kPad) ± 4 psid (27.5 kPad)

Preset, no calibration needed

— CONTROL

Cutout

Ͻ

15 psid (103 kPad)

Alert

Ͻ

18 psid (124 kPad)

Preset

LINE VOLTAGE — HIGH

Ͼ

110% for one minute

Preset, based on transformed line volt-
age to 24 vac rated-input to the Starter
Management Module. Also monitored at
PSIO power input.

— LOW

Ͻ

90% for one minute or

р

85% for 3 seconds

— SINGLE-CYCLE

Ͻ

50% for one cycle

COMPRESSOR MOTOR LOAD

Ͼ

110% for 30 seconds

Preset

Ͻ

10% with compressor running

Preset

Ͼ

10% with compressor off

Preset

STARTER ACCELERATION TIME
(Determined by inrush current
going below 100% compressor
motor load)

Ͼ

45 seconds

For chillers with reduced voltage me-
chanical and solid-state starters

Ͼ

10 seconds

For chillers with full voltage starters
(Configured on Service1 table)

STARTER TRANSITION

Ͼ

75 seconds

Reduced voltage starters only

CONDENSER FREEZE
PROTECTION

Energizes condenser pump relay if condenser
refrigerant temperature or condenser entering
water temperature is below the configured con-
denser freeze point temperature. Deenergizes
when the temperature is 5 F (3 C) above con-
denser freeze point temperature.

CONDENSER FREEZE POINT config-
ured in Service01 table with a default
setting of 34 F (1 C).

Flow Switches (Field Supplied)
Operate water pumps with chiller off. Manually
reduce water flow and observe switch for proper
cutout. Safety shutdown occurs when cutout time
exceeds 3 seconds.

CUT-OUT
SETTING
ADJUSTMENT
SCREW

30