Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides

A. SHUTDOWN WITH ON/OFF/RESET-OFF

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

MANUALLY STOPPED — PRESS

CCN OR LOCAL TO START

PIC in OFF mode, press the CCN or local softkey
to start unit.

TERMINATE PUMPDOWN MODE

TO SELECT CCN OR LOCAL

Enter the Control Test table and select Terminate
Lockout to unlock compressor.

SHUTDOWN IN PROGRESS

COMPRESSOR UNLOADING

Chiller unloading before shutdown due to Soft
Stop feature.

SHUTDOWN IN PROGRESS

COMPRESSOR DEENERGIZED

Chiller compressor is being commanded to stop.
Water pumps are deenergized within one minute.

ICE BUILD

OPERATION COMPLETE

Chiller shutdown from Ice Build operation.

B. TIMING OUT OR TIMED OUT

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

READY TO START IN XX MIN

UNOCCUPIED MODE

Time schedule for PIC is unoccupied. Chillers will
start only when occupied.

READY TO START IN XX MIN

REMOTE CONTACTS OPEN

Remote contacts have stopped chiller. Close con-
tacts to start.

READY TO START IN XX MIN

STOP COMMAND IN EFFECT

Chiller START/STOP on Status01 manually forced
to stop. Release value to start.

READY TO START IN XX MIN

RECYCLE RESTART PENDING

Chiller in recycle mode.

READY TO START

UNOCCUPIED MODE

Time schedule for PIC is UNOCCUPIED. Chiller
will start when occupied. Make sure the time and
date have been set on the Service menu.

READY TO START

REMOTE CONTACTS OPEN

Remote contacts have stopped chiller. Close con-
tacts to start.

READY TO START

STOP COMMAND IN EFFECT

Chiller START/STOP on Status01 manually forced
to stop. Release value to start.

READY TO START IN XX MIN

REMOTE CONTACTS CLOSED

Chiller timer counting down unit. Ready for start.

READY TO START IN XX MIN

OCCUPIED MODE

Chiller timer counting down unit. Ready for start.

READY TO START

REMOTE CONTACTS CLOSED

Chiller timers complete, unit start will commence.

READY TO START

OCCUPIED MODE

Chiller timers complete, unit start will commence.

STARTUP INHIBITED

LOADSHED IN EFFECT

CCN loadshed module commanding chiller to
stop.

READY TO START IN XX MIN

START COMMAND IN EFFECT

Chiller START/STOP on Status01 has been
manually forced to start. Chiller will start regard-
less of time schedule or remote contact status.

LEGEND

1CR

AUX

Compressor Start Contact

CA

P

Compressor Current

CCN

Carrier Comfort Network

CDFL

Condenser Water Flow

CHIL

S

S — Chiller Start/Stop

CHW

Chilled Water

CHWS

Chilled Water Supply

CHWR

Chiller Water Return

CMPD

Discharge Temperature

CRP

Condenser Pressure

CRT

Condenser Refrigerant

Temperature

ECW

Entering Chilled Water

ERT

Evaporator Refrigerant

Temperature

EVFL

Chilled Water Flow

GV

TRG — Target Guide Vane Position

LID

Local Interface Device

MTRB

Bearing Temperature

MTRW

Motor Winding Temperature

OILPD

Oil Pressure

OILT

Oil Sump Temperature

PIC

Product Integrated Control

PSIO

Processor Sensor

Input/Output Module

RLA

Rated Load Amps

RUN

AUX — Compressor Run Contact

SPR

PL

Spare Protective Limit Input

SMM

Starter Management

Module

STR

FLT

Starter Fault

TXV

Thermostatic Expansion

Valve

V

P

Line Voltage: Percent

V

REF

Voltage Reference

68