Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

I. NORMAL RUN OVERRIDES ACTIVE (ALERTS)

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

RUN CAPACITY

LIMITED

HIGH CONDENSER PRESSURE

CRP [VALUE]* exceeded limit of
[LIMIT]*. Condenser pressure override.

See Capacity Overrides, Table 4.
Correct operating condition, modify
setpoint, or release override.

RUN CAPACITY

LIMITED

HIGH MOTOR TEMPERATURE

MTRW [VALUE]* exceeded limit of
[LIMIT]*. Motor temperature override.

RUN CAPACITY

LIMITED

LOW EVAP REFRIG TEMP

ERT [VALUE]* exceeded limit of
[LIMIT]*. Check refrigerant charge level.

RUN CAPACITY

LIMITED

HIGH COMPRESSOR LIFT

Surge Prevention Override; lift too high
for compressor.

RUN CAPACITY

LIMITED

MANUAL GUIDE VANE TARGET

GV

TRG Run Capacity Limited:

Manual guide vane target.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or

alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.

J. OUT-OF-RANGE SENSOR FAILURES

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

SENSOR FAULT

LEAVING CHW TEMPERATURE

Sensor Fault: Check leaving CHW
sensor.

See sensor test procedure and
check sensors for proper operation
and wiring.

SENSOR FAULT

ENTERING CHW TEMPERATURE

Sensor Fault: Check entering CHW
sensor.

SENSOR FAULT

CONDENSER PRESSURE

Sensor Fault: Check condenser
pressure transducer.

SENSOR FAULT

EVAPORATOR PRESSURE

Sensor Fault: Check evaporator
pressure transducer.

SENSOR FAULT

BEARING TEMPERATURE

Sensor Fault: Check bearing
temperature sensor.

SENSOR FAULT

MOTOR WINDING TEMP

Sensor Fault: Check motor temperature
sensor.

SENSOR FAULT

DISCHARGE TEMPERATURE

Sensor Fault: Check discharge
temperature sensor.

SENSOR FAULT

OIL SUMP TEMPERATURE

Sensor Fault: Check oil sump
temperature sensor.

SENSOR FAULT

OIL PRESSURE TRANSDUCER

Sensor Fault: Check oil pressure
transducer.

NOTE: See Legend on page 68.