Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

C. IN RECYCLE SHUTDOWN

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

RECYCLE RESTART PENDING

OCCUPIED MODE

Unit in recycle mode, chilled water temperature is not
high enough to start.

RECYCLE RESTART PENDING

REMOTE CONTACT CLOSED

Unit in recycle mode, chilled water temperature is not
high enough to start.

RECYCLE RESTART PENDING

START COMMAND IN EFFECT

Chiller START/STOP on Status01 manually forced to
start, chilled water temperature is not high enough to
start.

RECYCLE RESTART PENDING

ICE BUILD MODE

Chiller in ICE BUILD mode. Chilled Water/Brine Tem-
perature is satisfied for Ice Build Setpoint temperature.

D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

PRESTART ALERT

STARTS LIMIT EXCEEDED

STARTS EXCESSIVE Compressor
Starts (8 in 12 hours)

Depress the RESET softkey if addi-
tional start is required. Reassess
start-up requirements.

PRESTART ALERT

HIGH MOTOR TEMPERATURE

MTRW [VALUE]* exceeded limit of
[LIMIT]*. Check motor temperature.

Check motor cooling line for proper
operation. Check for excessive
starts within a short time span.

PRESTART ALERT

HIGH BEARING TEMPERATURE

MTRB [VALUE]* exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.

Check oil heater for proper opera-
tion, check for low oil level, partially
closed oil supply valves, etc. Check
sensor accuracy.

PRESTART ALERT

HIGH DISCHARGE TEMP

CMPD [VALUE]* exceeded limit of
[LIMIT]*. Check discharge temperature.

Check sensor accuracy. Allow dis-
charge temperature to cool. Check
for excessive starts.

PRESTART ALERT

LOW REFRIGERANT TEMP

ERT [VALUE]* exceeded limit of
[LIMIT]*. Check refrigerant temperature.

Check transducer accuracy. Check
for low chilled water/brine supply
temperature.

PRESTART ALERT

LOW OIL TEMPERATURE

OILT [VALUE]* exceeded limit of
[LIMIT]*. Check oil temperature.

Check oil heater power, oil heater
relay. Check oil level.

PRESTART ALERT

LOW LINE VOLTAGE

V

P [VALUE]* exceeded limit of

[LIMIT]*. Check voltage suppy.

Check voltage supply. Check volt-
age transformers. Consult power
utility if voltage is low. Adjust voltage
potentiometer in starter for SMM
voltage input.

PRESTART ALERT

HIGH LINE VOLTAGE

V

P [VALUE]* exceeded limit of

[LIMIT]*. Check voltage supply.

Check voltage supply. Check volt-
age transformers. Consult power
utility if voltage is low. Adjust voltage
potentiometer in starter for SMM
voltage input.

PRESTART ALERT

HIGH CONDENSER PRESSURE

CRP [VALUE]* exceeded limit of
[LIMIT]*. Check condenser water and
transducer.

Check for high condenser water
temperature. Check transducer
accuracy.

*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is

the actual temperature, pressure, voltage, etc., at which the control tripped.

E. NORMAL OR AUTO.-RESTART

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

STARTUP IN PROGRESS

OCCUPIED MODE

Chiller starting. Time schedule is occupied.

STARTUP IN PROGRESS

REMOTE CONTACT CLOSED

Chiller starting. Remote contacts are closed.

STARTUP IN PROGRESS

START COMMAND IN EFFECT

Chiller starting. Chiller START/STOP on Status01 manu-
ally forced to start.

AUTORESTART IN PROGRESS

OCCUPIED MODE

Chiller starting. Time schedule is occupied.

AUTORESTART IN PROGRESS

REMOTE CONTACT CLOSED

Chiller starting. Remote contacts are closed.

AUTORESTART IN PROGRESS

START COMMAND IN EFFECT

Chiller starting. Chiller START/STOP on Status01 manu-
ally forced to start.

NOTE: See Legend on page 68.