Carrier 19XL User Manual

Page 54

Advertising
background image

19XL CHILLER EQUALIZATION WITH PUMPOUT
UNIT — The following procedure describes how to equal-
ize refrigerant pressure on an isolated 19XL chiller using the
pumpout unit.
1. Access the TERMINATE LOCKOUT mode in the Con-

trol Test.

2. Turn on the chilled water and condenser water pumps to

prevent possible freezing.

3. Open valve 4 on the pumpout unit and open valves 1a

and 1b on the chiller cooler and condenser, Fig. 27 and
28. Slowly open valve 2 on the pumpout unit to equalize
the pressure. This process will take approximately
15 minutes.

4. Once the pressures have equalized, the discharge isola-

tion valve, cooler isolation valve, optional hot gas bypass
isolation valve, and the refrigerant isolation valve can be
opened. Close valves 1a and 1b, and all pumpout unit
valves.

Whenever turning the discharge isolation valve, be
sure to reattach the valve locking device. This will
prevent the valve from opening or closing during serv-
ice work or during chiller operation.

The full refrigerant charge on the 19XL will vary with

chiller components and design conditions, indicated on the
job data specifications. An approximate charge may be found
by adding the condenser charge to the cooler charge listed in
Table 8.

Always operate the condenser and chilled water pumps

during charging operations to prevent freeze-ups. Use the
Control Test Terminate Lockout to monitor conditions and
start the pumps.

If the chiller has been shipped with a holding charge , the

refrigerant will be added through the refrigerant charging valve
(Fig. 27 and 28, valve 7) or to the pumpout charging con-
nection. First evacuate the nitrogen holding charge from the

vessels. Charge the refrigerant as a gas until the system pres-
sure exceeds 68 psig (469 kPa); [35 psig (141 kPa)]. After
the chiller is beyond this pressure the refrigerant should be
charged as a liquid until all of the recommended refrigerant
charge has been added.

TRIMMING REFRIGERANT CHARGE — The 19XL is
shipped with the correct charge for the design duty of the
chiller. Trimming the charge can be best accomplished when
design load is available. To trim, check the temperature
difference between leaving chilled water temperature and
cooler refrigerant temperature at full load design conditions.
If necessary, add or remove refrigerant to bring the tempera-
ture difference to design conditions or minimum differential.

Table 8 — Refrigerant Charges*

COOLER

SIZE

19XL TOTAL REFRIGERANT CHARGE

Design I

Chiller

Design II

Chiller

HCFC-22

HFC-134a

lb

kg

lb

kg

lb

kg

40

1420

640

1100

499

900

409

41

1490

680

1150

522

950

431

42

1550

700

1250

568

1000

454

43

1600

730

1350

613

1050

477

50

1850

840

1500

681

1100

499

51

1900

860

1600

726

1200

545

52

1980

900

1750

795

1300

590

53

2050

930

1850

840

1350

613

55

1900

863

1550

704

56

2200

999

1650

749

57

2500

1135

1750

795

58

2700

1226

1900

863

*Design I chillers use HCFC-22. Design II chillers use either HCFC-22

or HFC-134a.

NOTES:
1. The size of the cooler determines refrigerant charge for the entire

chiller.

2. Design I chillers have float chambers.
3. Design II chillers have linear floats.

54

Advertising