Carrier 19XL User Manual

Page 24

Advertising
background image

Table 2 — LID Screens (cont)

EXAMPLE 7 — SERVICE1 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT .

5. Scroll down to highlight SERVICE1.
6. Press SELECT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

Motor Temp Override

150-200 (66-93)

DEG F (DEG C)

mt

over

200 (93)

Cond Press Override

150-245 (1034-1689)

[90-200 (620-1379)]

PSI (kPa)

cp

over

195 (1345) [125 (862)]

Refrig Override Delta T

2-5 (1-3)

DEG F (DEG C)

ref

over

3

(1.6

)

Chilled Medium

Water/Brine

medium

WATER

Brine Refrig Trippoint

8-40 (–13.3-4)

DEG F (DEG C)

br

trip

33 (1)

Compr Discharge Alert

125-200 (52-93)

DEG F (DEG C)

cd

alert

200 (93)

Bearing Temp Alert

175-185 (79-85)

DEG F (DEG C)

tb

alert

175 (79)

Water Flow Verify Time

0.5-5

MIN

wflow

t

5

Oil Press Verify Time

15-300

SEC

oilpr

t

15

Water/Brine Deadband

0.5-2.0 (0.3-1.1)

DEG F (DEG C)

cw

db

1.0 (0.6)

Recycle Restart Delta T

2.0-10.0 (1.1-5.6)

DEG F (DEG C)

rcyc

dt

5 (2.8)

Recycle Shutdown Delta T

0.5-4.0 (0.27-2.2)

DEG F (

DEG C)

rcycs

dt

1.0 (0.6)

Surge Limit/HGBP Option

0/1

srg

hgbp

0

Select: Surge=0, HGBP=1
Surge/HGBP Delta T1

0.5-15 (0.3-8.3)

DEG F (DEG C)

hgb

dt1

1.5 (0.8)

Surge/HGBP Delta P1

50-170 (345-1172)

[30-170 (207-1172)]

PSI (kPA)

hgb

dp1

75 (517) [50 (345)]

Min. Load Points (T1/P1)
Surge/HGBP Delta T2

0.5-15 (0.3-8.3)

DEG F (DEG C)

hgb

dt2

10 (5.6)

Surge/HGBP Delta P2

50-170 (345-1172)
[30-170 (207-1172)]

PSI (kPa)

hgb

dp2

170 (1172) [85 (586)]

Full Load Points (T2/P2)
Surge/HGBP Deadband

1-3 (0.6-1.6)

DEG F (DEG C)

hgb

dp

1 (0.6)

Surge Delta Percent Amps

10-50

%

surge

a

25

Surge Time Period

1-5

MIN

surge

t

2

Demand Limit Source

0/1

dem

src

0

Select: Amps=0, Load=1
Amps Correction Factor

1-8

corfact

3

Motor Rated Load Amps

1-9999

AMPS

a

fs

200

Motor Rated Line Voltage

1-9999

VOLTS

v

fs

460

Meter Rated Line kW

1-9999

kW

kw

fs

600

Line Frequency

0/1

HZ

freq

0

Select: 0=60 Hz, 1=50 Hz
Compr Starter Type

REDUCE/FULL

starter

REDUCE

Condenser Freeze Point

–20-35 (–28.9-1.7)

DEG F (DEG C)

cdfreeze

34 (1)

Soft Stop Amps Threshold

40-100

%

softstop

100

NOTES:
1. Condenser Freeze Point and Softstop Amps Threshold are only selectable/readable on PSIO Software Versions 09 and higher.
2. Values in [ ] indicate HFC-134a values.
3.

= delta degrees.