Table 2 — LID Screens (cont)

EXAMPLE 5 — CONFIGURATION (CONFIG) DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT .

5. Scroll down to highlight CONFIG.

6. Press SELECT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

RESET TYPE 1
Degrees Reset at 20 mA

–30-30 (–17-17)

DEG F (DEG C)

deg

20ma

10

(6

)

RESET TYPE 2
Remote Temp (No Reset)

–40-245 (–40-118)

DEG F (DEG C)

res

rt1

85 (29)

Remote Temp (Full Reset)

–40-245 (–40-118)

DEG F (DEG C)

res

rt2

65 (18)

Degrees Reset

–30-30 (–17-17)

DEG F (DEG C)

res

rt

10

(6

)

RESET TYPE 3
CHW Delta T (No Reset)

0-15 (0-8)

DEG F (DEG C)

restd

1

10

(6

)

CHW Delta T (Full Reset)

0-15 (0-8)

DEG F (DEG C)

restd

2

0

(0

)

Degrees Reset

–30-30 (–17-17)

DEG F (DEG C)

deg

chw

5

(3

)

Select/Enable Reset Type

0-3

res

sel

0

ECW CONTROL OPTION

DISABLE/ENABLE

ecw

opt

DISABLE

Demand Limit At 20 mA

40-100

%

dem

20ma

40

20 mA Demand Limit Option

DISABLE/ENABLE

dem

sel

DISABLE

Auto Restart Option

DISABLE/ENABLE

astart

DISABLE

Remote Contacts Option

DISABLE/ENABLE

r

contact

DISABLE

Temp Pulldown Deg/Min

2-10

tmp

ramp

3

Load Pulldown %/Min

5-20

kw

ramp

10

Select Ramp Type:

0/1

ramp

opt

1

Temp = 0, Load = 1

Loadshed Group Number

0-99

ldsgrp

0

Loadshed Demand Delta

0-60

%

ldsdelta

20

Maximum Loadshed Time

0-120

MIN

maxldstm

60

CCN Occupancy Config:

Schedule Number

3-99

occpcxxe

3

Broadcast Option

DISABLE/ENABLE

occbrcst

DISABLE

ICE BUILD Option

DISABLE/ENABLE

ibopt

DISABLE

ICE BUILD TERMINATION

0 =Temp, 1 =Contacts, 2 =Both

0-2

ibterm

0

ICE BUILD Recycle Option

DISABLE/ENABLE

ibrecyc

DISABLE

NOTE:

= delta degrees.

EXAMPLE 6 — LEAD/LAG CONFIGURATION DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT .

5. Scroll down to highlight Lead/Lag.

6. Press SELECT .

LEAD/LAG CONFIGURATION SCREEN

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

LEAD/LAG SELECT

DISABLE =0, LEAD =1,
LAG =2, STANDBY =3

0-3

leadlag

0

Load Balance Option

DISABLE/ENABLE

loadbal

DISABLE

Common Sensor Option

DISABLE/ENABLE

commsens

DISABLE

LAG Percent Capacity

25-75

%

lag

per

50

LAG Address

1-236

lag

add

92

LAG START Timer

2-60

MIN

lagstart

10

LAG STOP Timer

2-60

MIN

lagstop

10

PRESTART FAULT Timer

0-30

MIN

preflt

5

STANDBY Chiller Option

DISABLE/ENABLE

stndopt

DISABLE

STANDBY Percent Capacity

25-75

%

stnd

per

50

STANDBY Address

1-236

stnd

add

93

NOTE: The Lead/Lag Configuration table is available on PSIO Software Version 09 and higher.

23