Carrier 19XL User Manual

Page 52

Advertising
background image

Table 6 — Amps Correction Factors

for 19XL Motors

VOLT/

Hz

MOTOR CODE

CB

CC

CD

CE

CL

CM

CN

CP

CQ

CR

200/60

4

5

3

6

3

2

3

2

2

2

208/60

5

5

5

8

4

2

4

2

2

2

220/60

3

4

2

2

2

3

1

1

1

1

230/60

5

6

4

4

3

5

2

2

2

2

240/60

5

6

4

4

3

8

2

2

2

2

360/60

4

2

4

2

2

2

1

1

1

1

380/60

7

4

6

4

4

5

3

2

2

2

400/60

7

5

8

4

4

5

3

2

3

4

440/60

3

3

2

2

1

1

1

1

3

4

460/60

5

4

3

2

2

2

2

2

5

6

480/60

7

5

4

3

3

3

3

3

7

8

550/60

4

2

3

2

1

2

3

2

2

2

575/60

4

4

4

2

2

3

4

3

3

3

600/60

8

5

6

4

3

4

6

5

4

4

3300/60

4

4

4

1

2

3

3

3

2

2

2400/60

4

4

3

3

2

3

2

2

3

3

4160/60

4

4

3

3

2

3

2

2

3

3

220/50

3

1

2

2

2

3

2

1

1

1

230/50

4

2

2

3

2

4

3

2

1

1

240/50

5

3

5

4

3

5

3

3

2

2

320/50

2

2

2

2

1

1

1

1

3

3

346/50

4

4

3

3

3

2

1

2

3

4

360/50

5

5

4

4

4

2

2

2

8

8

380/50

5

2

3

3

3

2

4

2

2

2

400/50

6

4

4

5

4

3

6

4

3

3

415/50

8

5

5

6

5

4

7

5

4

4

3000/50

3

2

2

3

2

3

1

2

1

2

3300/50

4

3

3

3

3

4

2

2

1

2

MODIFY EQUIPMENT CONFIGURATION IF NECES-
SARY — The Equipment Configuration table has tables to
select and view or modify. Carrier’s certified drawings will
have the configuration values required for the jobsite. Modify
these tables only if requested.

Config Table Modifications — Change the values in this table
per job data. See certified drawings for values. Modifica-
tions include:

• chilled water reset
• entering chilled water control (Enable/Disable)
• 4-20 mA demand limit
• auto. restart option (Enable/Disable)
• remote contact option (Enable/Disable)

Owner-Modified CCN Tables— The following tables are de-
scribed for reference only.

Occdef Table Modifications — The Occdef tables contain
the Local and CCN time schedules, which can be modified
here, or in the Schedule screen as described previously.
Holidef Table Modifications — The Holidef tables configure
the days of the year that holidays are in effect. See the holi-
day

paragraphs

in

the

Controls

section

for

more

details.
Brodefs Table Modifications — The Brodefs table defines
the outside-air temperature sensor and humidity sensor if one
is to be installed. It will define the start and end of day-
light savings time. Enter the dates for the start and end of
daylight savings if required for the location. Brodefs also
will activate the Broadcast function which enables the holi-
day periods that are defined on the LID.
Other Tables — The Alarmdef, Cons-def, and Runt-def con-
tain tables for use with a CCN system. See the applicable
CCN manual for more information on these tables.
These tables can only be defined through a CCN Building
Supervisor.

CHECK VOLTAGE SUPPLY — Access the Status 01 screen
and read the actual line voltage. This reading should be equal

to the incoming power to the starter. Use a voltmeter to check
incoming power at the starter power leads. If the readings
are not equal, an adjustment can be made to the 24-v input
to the SMM at the potentiometer located in the low-voltage
section to equalize the two readings.

PERFORM AN AUTOMATED CONTROL TEST — Check
the safety controls status by performing an automated con-
trols test. Access the Control Test table and select the
Automated Tests function (Table 8).

The Automated Control Test will check all outputs and

inputs for function. It will also set the refrigerant type. The
compressor must be in the OFF mode in order to operate the
controls test and the 24-v input to the SMM must be in range
(per line voltage percent on Status01 table). The OFF mode
is caused by pressing the STOP pushbutton on the LID. Each
test will ask the operator to confirm that the operation is oc-
curring, and whether or not to continue. If an error occurs,
the operator has the choice to try to address the problem as
the test is being done, or to note the problem and proceed to
the next test.

NOTE: If during the Control Test the guide vanes do not
open, check to see that the low pressure alarm is not active.
(This will cause the guide vanes to close).
NOTE: The oil pump test will not energize the oil pump if
cooler pressure is below –5 psig (–35 kPa).

When the test is finished, or the EXIT softkey is pressed,

the test will be stopped and the Control Test menu will be
displayed. If a specific automated test procedure is not
completed, access the particular control test to test the func-
tion when ready. The Control Test menu is described as
follows:

Automated Tests

As described above, a complete
control test.

PSIO Thermistors

Check of all PSIO thermistors only.

Options Thermistors

Check of all options boards
thermistors.

Transducers

Check of all transducers.

Guide Vane Actuator

Check of the guide vane operation.

Pumps

Check operation of pump outputs,
either all pumps can be activated,
or individual pumps. The test will
also test the associated input such
as flow or pressure.

Discrete Outputs

Activation of all on/off outputs or
individually.

Pumpdown/Lockout

Pumpdown prevents the low refrig-
erant alarm during evacuation so
refrigerant can be removed from
the unit, locks the compressor off,
and starts the water pumps.

Terminate Lockout

To charge refrigerant and enable
the chiller to run after pumpdown
lockout.

Refrigerant Type*

Sets type of refrigerant used:

HCFC-22 or HFC-134a.

*Make sure to Attach to Local Device after changing refrigerant type.

Refer to Selecting Refrigerant Type section on page 50.

Check Optional Pumpout System Controls and
Compressor —

Controls include an on/off switch, a 3-amp

fuse, the compressor overloads, an internal thermostat, a com-
pressor contactor, and a refrigerant high pressure cutout. The
high pressure cutout is factory set to open at 220 ± 5 psig
(1250 ± 34 kPa), and automatically reset at 185 + 0,
−7 psig (1280 +0,–48 kPa) with HCFC-22. HFC-134a units
open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa).
Check that the water-cooled condenser has been connected.

52