Table 2 — LID Screens (cont)

EXAMPLE 8 — SERVICE2 DISPLAY SCREEN

To access this display from the LID default screen:

1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT .

5. Scroll down to highlight SERVICE2.

6. Press SELECT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source

0,1

res

20 ma

0

DEMAND 20 mA Power Source

0,1

dem

20 ma

0

SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
CHWS Temp Enable

0-2

chws

en

0

CHWS Temp Alert

–40-245 (–40-118)

DEG F (DEG C)

chws

al

245 (118)

CHWR Temp Enable

0-2

chwr

en

0

CHWR Temp Alert

–40-245 (–40-118)

DEG F (DEG C)

chwr

al

245 (118)

Reset Temp Enable

0-2

rres

en

0

Reset Temp Alert

–40-245 (–40-118)

DEG F (DEG C)

rres

al

245 (118)

Spare Temp 1 Enable

0-2

spr1

en

0

Spare Temp 1 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr1

al

245 (118)

Spare Temp 2 Enable

0-2

spr2

en

0

Spare Temp 2 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr2

al

245 (118)

Spare Temp 3 Enable

0-2

spr3

en

0

Spare Temp 3 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr3

al

245 (118)

OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 mA Power Source

0,1

sp1

20 ma

0

SPARE 2 20 mA Power Source

0,1

sp2

20 ma

0

SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
Spare Temp 4 Enable

0-2

spr4

en

0

Spare Temp 4 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr4

al

245 (118)

Spare Temp 5 Enable

0-2

spr5

en

0

Spare Temp 5 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr5

al

245 (118)

Spare Temp 6 Enable

0-2

spr6

en

0

Spare Temp 6 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr6

al

245 (118)

Spare Temp 7 Enable

0-2

spr7

en

0

Spare Temp 7 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr7

al

245 (118)

Spare Temp 8 Enable

0-2

spr8

en

0

Spare Temp 8 Alert

–40-245 (–0-118)

DEG F (DEG C)

spr8

al

245 (118)

Spare Temp 9 Enable

0-2

spr9

en

0

Spare Temp 9 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr9

al

245 (118)

NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp Alert’’ threshold for each point listed. If the
‘‘Enable’’ is set to 1, a value above the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp
Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.

EXAMPLE 9 — SERVICE3 DISPLAY SCREEN

To access this display from the LID default screen:

1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT .

5. Scroll down to highlight SERVICE3.

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

Proportional Inc Band

2-10

gv

inc

6.5

Proportional Dec Band

2-10

gv

de

6.0

Proportional ECW Gain

1-3

gv

ecw

2.0

Guide Vane Travel Limit

30-100

%

gv

lim

50

25