Physical data – Carrier 19XL User Manual

Page 85

Advertising
background image

Physical Data —

Tables 12-17 and Fig. 47-51 pro-

vide additional information regarding compressor fits and

clearances, physical and electrical data, and wiring sche-
matics for operator convenience during troubleshooting.

Table 12 — Heat Exchanger Data

COOLER

VESSEL

HEAT

EXCHANGER

CODE

NUMBER

OF TUBES

RIGGING WEIGHTS

VESSEL CHARGE

Dry Wt.

Refrigerant

Volume

of Water

Design I

Design II

Design I

Design II

HCFC-22

HCFC-22

HFC-134a

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Gal

L

COOLER

40

201

5000

2275

5340

2422

1020

463

750

341

550

250

53

201

41

227

5150

2350

5485

2488

1090

494

800

363

600

272

58

220

42

257

5325

2425

5655

2565

1150

522

900

408

650

295

64

242

43

290

5500

2500

5845

2651

1200

544

1000

454

700

318

71

269

50

314

6625

3000

7020

3184

1450

658

1150

522

750

341

79

299

51

355

6850

3100

7255

3291

1500

680

1250

568

850

386

87

329

52

400

7100

3225

7510

3406

1580

717

1400

636

950

431

96

363

53

445

7375

3350

7770

3524

1650

748

1500

681

1000

454

104

394

55

201

8510

3860

1410

640

1060

481

104

395

56

227

8845

4012

1710

776

1160

527

115

438

57

257

9205

4175

2010

913

1260

572

128

486

58

290

9575

4343

2210

1003

1410

640

140

531

CONDENSER

VESSEL

HEAT

EXCHANGER

CODE

NUMBER

OF TUBES

RIGGING WEIGHTS

VESSEL CHARGE

Dry Wt.

Refrigerant

Volume

of Water

Design I

Design II

Design I

Design II

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Gal

L

CONDENSER

40

218

5050

2100

4855

2202

400

181

350

159

56

212

41

246

5200

2350

5010

2272

400

181

350

159

62

235

42

279

5375

2450

5180

2350

400

181

350

159

68

257

43

315

5575

2525

5370

2436

400

181

350

159

75

284

50

347

7050

3200

6750

3062

400

181

350

159

84

318

51

387

7275

3300

6960

3157

400

181

350

159

92

348

52

432

7500

3400

7200

3266

400

181

350

159

101

382

53

484

7775

3525

7475

3391

400

181

350

159

110

416

55

218

8345

3785

490

222

112

423

56

246

8635

3917

490

222

123

466

57

279

8980

4073

490

222

135

513

58

315

9370

4250

490

222

149

565

NOTES:
1. Design I chillers are equipped with a float box, and chiller weight is based on a 150 psi (1034 kPa)

waterbox with 2 pass arrangement.

2. Design II chillers are equipped with a linear float, and chiller weight is based on a 300 psi (2068 kPa)

waterbox with 1 pass arrangement.

3. Total refrigerant charge is equal to the cooler charge added to the condenser charge.

Table 13 — Additional Data for Marine Waterboxes*

HEAT EXCHANGER

FRAME, PASS

ENGLISH

SI

Rigging Wt

(lb)

Water Volume

(gal)

Rigging Wt

(kg)

Water Volume

(L)

Cooler

Condenser

Cooler

Condenser

Cooler

Condenser

Cooler

Condenser

FRAME 4, 2 PASS

1115

660

69

51

506

300

261

193

FRAME 4, 1 & 3 PASS

2030

1160

138

101

922

527

524

384

FRAME 5, 2 PASS

1220

935

88

64

554

424

331

243

FRAME 5, 1 & 3 PASS

2240

1705

175

128

1017

774

663

486

*Add to heat exchanger weights and volumes for total weight or volume.

85