Carrier 19XL User Manual

Page 26

Advertising
background image

Table 2 — LID Screens (cont)

EXAMPLE 10 — MAINTENANCE (MAINT01) DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight ALGORITHM STATUS.

4. Press SELECT .

5. Scroll down to highlight MAINT01.

DESCRIPTION

RANGE/STATUS

UNITS

REFERENCE POINT NAME

CAPACITY CONTROL
Control Point

10-120 (–12.2-48.9)

DEG F (DEG C)

ctrlpt

Leaving Chilled Water

–40-245 (–40-118)

DEG F (DEG C)

LCW

Entering Chilled Water

–40-245 (–40-118)

DEG F (DEG C)

ECW

Control Point Error

–99-99 (–55-55)

DEG F (DEG C)

cperr

ECW Delta T

–99-99 (–55-55)

DEG F (DEG C)

ecwdt

ECW Reset

–99-99 (–55-55)

DEG F (DEG C)

ecwres

LCW Reset

–99-99 (–55-55)

DEG F (DEG C)

lcwres

Total Error + Resets

–99-99 (–55-55)

DEG F (DEG C)

error

Guide Vane Delta

–2-2

%

gvd

Target Guide Vane Pos

0-100

%

GV

TRG

Actual Guide Vane Pos

0-100

%

GV

ACT

Proportional Inc Band

2-10

gv

inc

Proportional Dec Band

2-10

gv

dec

Proportional ECW Gain

1-3

gv

ecw

Water/Brine Deadband

0.5-2 (0.3-1.1)

DEG F (DEG C)

cwdb

NOTE: Overriding is not supported on this maintenance screen. Active overrides show the associated point in alert (*). Only values with capital letter
reference point names are variables available for read operation.

EXAMPLE 11 — MAINTENANCE (MAINT02) DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight CONTROL ALGORITHM STATUS.

4. Press SELECT .

5. Scroll down to highlight MAINT02.

6. Press SELECT .

DESCRIPTION

RANGE/STATUS

UNITS

REFERENCE POINT NAME

OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP

–40-245 (–40-118)

DEG F (DEG C)

MTRW

Override Threshold

150-200 (66-93)

DEG F (DEG C)

mt

over

CONDENSER PRESSURE

–6.7-420 (–42-2896)

PSI (kPa)

CRP

Override Threshold

90-245 (621-1689)

PSI (kPa)

cp

over

EVAPORATOR REFRIG TEMP

–40-245 (–40-118)

DEG F (DEG C)

ERT

Override Threshold

2-45 (1-7.2)

DEG F (DEG C)

rt

over

DISCHARGE TEMPERATURE

–40-245 (–40-118)

DEG F (DEG C)

CMPD

Alert Threshold

125-200 (52-93)

DEG F (DEG C)

cd

alert

BEARING TEMPERATURE

–40-245 (–40-118)

DEG F (DEG C)

MTRB

Alert Threshold

175-185 (79-85)

DEG F (DEG C)

tb

alert

NOTE: Overriding is not supported on this maintenance screen. Active overrides show the associated point in alert (*). Only values with capital letter
reference point names are variables available for read operation.

26

Advertising