Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

L. CHILLER ALERTS

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

RECYCLE ALERT

HIGH AMPS AT SHUTDOWN

High Amps at Recycle: Check guide vane
drive.

Check that guide vanes are closing.
Check motor amps correction cali-
bration is correct. Check actuator for
proper operation.

SENSOR FAULT ALERT

LEAVING COND WATER
TEMP

Sensor Fault: Check leaving condenser
water sensor.

Check sensor. See sensor test
procedure.

SENSOR FAULT ALERT

ENTERING COND WATER
TEMP

Sensor Fault: Check entering condenser
water sensor.

LOW OIL PRESSURE
ALERT

CHECK OIL FILTER

Low Oil Pressure Alert: Check oil

Check oil filter. Check for improper
oil level or temperature.

AUTORESTART PENDING POWER LOSS

V

P Power Loss: Check voltage supply.

Check power supply if there are ex-
cessive compressor starts occurring.

AUTORESTART PENDING LOW LINE VOLTAGE

V

P [VALUE]* exceeded limit of

[LIMIT].* Check voltage supply.

AUTORESTART PENDING HIGH LINE VOLTAGE

V

P [VALUE]* exceeded limit of

[LIMIT].* Check voltage supply.

SENSOR ALERT

HIGH DISCHARGE TEMP

CMPD [VALUE]* exceeded limit of
[LIMIT].* Check discharge temperature.

Discharge temperature exceeded
the alert threshold. Check entering
condenser water temperature.

SENSOR ALERT

HIGH BEARING
TEMPERATURE

MTRB [VALUE]* exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.

Thrust bearing temperature ex-
ceeded the alert threshold. Check
for closed valves, improper oil level
or temperatures.

CONDENSER PRESSURE
ALERT

PUMP RELAY ENERGIZED

CRP High Condenser Pressure
[LIMIT]*. Pump energized to reduce
pressure.

Check ambient conditions. Check
condenser pressure for accuracy.

RECYCLE ALERT

EXCESSIVE RECYCLE
STARTS

Excessive recycle starts.

The chiller load is too small to keep
the chiller on line and there have
been more than 5 restarts in 4
hours. Increase chiller load, adjust
hot gas bypass, increase RECYCLE
RESTART DELTA T.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or

alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.

M. SPARE SENSOR ALERT MESSAGES

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

SPARE SENSOR ALERT

COMMON CHWS SENSOR

Sensor Fault:
Check common CHWS sensor.

Check alert temperature set points
on Equipment Service, SERVICE2
LID table. Check sensor for accu-
racy if reading is not accurate.

SPARE SENSOR ALERT

COMMON CHWR SENSOR

Sensor Fault:
Check common CHWR sensor.

SPARE SENSOR ALERT

REMOTE RESET SENSOR

Sensor Fault:
Check remote reset temperature sensor.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 1

Sensor Fault:
Check temperature sensor — Spare 1.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 2

Sensor Fault:
Check temperature sensor — Spare 2.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 3

Sensor Fault:
Check temperature sensor — Spare 3.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 4

Sensor Fault:
Check temperature sensor — Spare 4.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 5

Sensor Fault:
Check temperature sensor — Spare 5.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 6

Sensor Fault:
Check temperature sensor — Spare 6.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 7

Sensor Fault:
Check temperature sensor — Spare 7.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 8

Sensor Fault:
Check temperature sensor — Spare 8.

SPARE SENSOR ALERT

TEMP SENSOR — SPARE 9

Sensor Fault:
Check temperature sensor — Spare 9.

NOTE: See Legend on page 68.