NOTES:

1.

Contactors

2M

and

S

are

mechanically

interlocked.

2.

T

ransition

resistor

fault

protector

(TRFP)

is

preset

to

trip

if

transition

contactor

(1A)

remains

energized

for

longer

than

one

second.

3.

When

optional

phase

loss

reversal

relay

(PMR)

or

phase

loss,

phase

reversal,

overvoltage,

undervoltage

relay

(PMR

VR)

is

not

provided,

terminals

3-13A

and

3-13B

are

jumpered

together

.

4.

When

optional

ground

fault

is

not

provided,

terminals

3-13B

and

3-13C

are

jumpered

together

.

5.

This

oil

pump

circuit

breaker

and

terminal

board

TB7

are

provided

only

on

start-

ers

for

centrifugal

machines.

6.

POT

to

be

adjusted

to

24

v

a

t

rated

line

voltage.

7.

CT4

and

CT5

are

provided

only

when

the

optional

watt

transducer

is

provided.

8.

These

3

wires

to

the

ammeter

switch

are

connected

together

only

when

the

optional

3-phase

ammeter

is

not

provided.

9.

PMR

TR

is

provided

only

if

the

optional

phase

loss

phase

reversal

relay

(PMR)

is

provided.

The

combination

PMR

VR

has

an

internal

time

delay

and

does

not

require

PMR

TR.

10.

Connections

on

the

above

schematic

are

numbered

to

match

the

markings

on

the

control

wires

within

the

starter

.

Wires

entering

terminal

boards

are

marked

with

the

terminal

number

.

1

1

.

Oil

pump

AUX.

contact

not

supplied

on

screw

machines.

NOTE:

Optional

features

are

indicated

by

bold

dotted

boxes.

Yellow

wires

remain

energized

when

main

disconnect

is

of

f.

Fig.

51

T

ypical

W

ye-Delta

Unit

Mounted

Starter

W

iring

Schematic

(cont)