Table 2 — LID Screens (cont)

EXAMPLE 12 — MAINTENANCE (MAINT03) DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight CONTROL ALGORITHM STATUS.

4. Press SELECT .

5. Scroll down to highlight MAINT03.

6. Press SELECT .

DESCRIPTION

RANGE/STATUS

UNITS

REFERENCE POINT NAME

SURGE/HGBP ACTIVE ?

NO/YES

Active Delta P

0-200 (0-1379)

PSI (kPa)

dp

a

Active Delta T

0-200 (0-111)

DEG F (DEG C)

dt

a

Calculated Delta T

0-200 (0-111)

DEG F (DEG C)

dt

c

Surge Protection Counts

0-12

spc

NOTE: Override is not supported on this maintenance screen. Only values with capital letter reference point names are variables available for read
operation.

EXAMPLE 13 — MAINTENANCE (MAINT04 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight CONTROL ALGORITHM STATUS.

4. Press SELECT .

5. Scroll down to highlight MAINT04.

6. Press SELECT .

DESCRIPTION

RANGE/STATUS

UNITS

REFERENCE POINT NAME

LEAD/LAG: Configuration

DISABLE,LEAD,LAG,STANDBY, INVALID

leadlag

Current Mode

DISABLE,LEAD,LAG,STANDBY, CONFIG

llmode

Load Balance Option

DISABLE/ENABLE

loadbal

LAG Start Time

0-60

MIN

lagstart

LAG Stop Time

0-60

MIN

lagstop

Prestart Fault Time

0-30

MIN

preflt

Pulldown: Delta T/Min

2-10 F/min (1.1-5.5 C/min)

DEG F/min

pull

dt

Satisfied?

No/Yes

(

DEG C/min)

pull

sat

LEAD CHILLER in Control

No/Yes

leadctrl

LAG CHILLER: Mode

Reset,Off,Local,CCN

lagmode

Run Status

Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown

lagstat

Start/Stop

Stop,Start,Retain

lag

s

s

Recovery Start Request

No/Yes

lag

rec

STANDBY CHILLER: Mode

Reset,Off,Local,CCN

stdmode

Run Status

Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown

stdstat

Start/Stop

Stop,Start,Retain

std

s

s

Recovery Start Request

No/Yes

std

rec

NOTES:
1. Only values with capital letter reference point names are variables available for read operation. Forcing is not supported on this maintenance

screen.

2. The MAINT04 screen is available on PSIO Software Version 09 and higher.
3.

= delta degrees.

27