Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

UNAUTHORIZED
OPERATION

UNIT SHOULD BE
STOPPED

CA

P Emergency: Compressor

running without control authorization.

Compressor is running with more than
10% RLA and control is trying to shut it
down. Throw power off to compressor if
unable to stop. Determine cause before
repowering.

POTENTIAL FREEZE-UP

EVAP PRESS/TEMP
TOO LOW

ERT Emergency: Freeze-up
prevention.

Determine cause. If pumping refrigerant
out of chiller, stop operation and go over
pumpout procedures.

FAILURE TO STOP

DISCONNECT POWER

RUN

AUX Emergency: DISCON-

NECT POWER.

Starter and run and start contacts are
energized while control tried to shut
down. Disconnect power to starter.

LOSS OF
COMMUNCIATION

WITH STARTER

Loss of Communication with Starter:
Check chiller.

Check wiring from PSIO to SMM. Check
SMM module troubleshooting procedures.

STARTER CONTACT
FAULT

ABNORMAL 1CR OR
RUN AUX

1CR

AUX Starter Contact Fault:

Check 1CR/1M aux. contacts.

Starter run and start contacts energized
while chiller was off. Disconnect power.

POTENTIAL FREEZE UP

COND PRESS/TEMP
TOO LOW

CRT [VALUE] exceeded limit of
[LIMIT]* Emergency: Freeze-up
prevention.

The condenser pressure transducer is
reading a pressure that could freeze the
water in the condenser tubes. Check for
condenser refrigerant leaks, bad trans-
ducers, or transferred refrigerant. Place
the unit in Pumpdown mode to eliminate
ALARM if vessel is evacuated.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or

alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

RUNNING — RESET ACTIVE

4-20MA SIGNAL

Reset program active based upon Config table setup.

RUNNING — RESET ACTIVE

REMOTE SENSOR CONTROL

RUNNING — RESET ACTIVE

CHW TEMP DIFFERENCE

RUNNING — TEMP CONTROL

LEAVING CHILLED WATER

Default method of temperature control.

RUNNING — TEMP CONTROL

ENTERING CHILLED WATER

ECW control activated on Config table.

RUNNING — TEMP CONTROL

TEMPERATURE RAMP LOADING

Ramp loading in effect. Use Service1 table to modify.

RUNNING — DEMAND LIMITED

BY DEMAND RAMP LOADING

Ramp loading in effect. Use Service1 table to modify.

RUNNING — DEMAND LIMITED

BY LOCAL DEMAND SETPOINT

Demand limit setpoint is

Ͻ

actual demand.

RUNNING — DEMAND LIMITED

BY 4-20MA SIGNAL

Demand limit is active based on Config table setup.

RUNNING — DEMAND LIMITED

BY CCN SIGNAL

RUNNING — DEMAND LIMITED

BY LOADSHED/REDLINE

RUNNING — TEMP CONTROL

HOT GAS BYPASS

Hot Gas Bypass is energized. See surge prevention
in the control section.

RUNNING — DEMAND LIMITED

BY LOCAL SIGNAL

Active demand limit manually overridden or Status01
table.

RUNNING — TEMP CONTROL

ICE BUILD MODE

Chiller is running under Ice Build temperature control.

NOTE: See Legend on page 68.