6.0 Mechanical

(cont’d)

FIGURE 4B - Refrigerant Piping on a PreevA® Split System with

the Condensing Unit Installed at a Lower Level than the Air

Handler Unit

CONDENSING UNIT INSTALLED AT GROUND LEVEL

FROM

AIR

HANDLER

REPRESENTATIVE

TRAPS

*Field-supplied

per NEC.

**Field-supplied

SIGHT GLASS/

MOISTURE

INDICATOR **

AIR HANDLER

UNIT WITH A

TWO-CIRCUIT (1/3-2/3)

COOLING COIL

FOR R-410A

REFRIGERANT

NOTES:

1. All piping must follow standard piping techniques for R-410A refrigerant. Refer to ASHRAE Guide and ASME Informational Standards for

piping information. Comply with CSA Mechanical Refrigeration Code CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or

provincial requirements.

2. All wiring must comply with all applicable local and national codes.

3. Wiring and piping shown are general points-of-connection guides only and are not intended to apply to or include all details for a specific

installation. Refer to ASHRAE Guide Section 15 for piping details.

4. Internal factory-supplied TXV’s on PREEVA air handler unit are not shown. (Air handler must have properly sized thermal expansion

valves.)

5. Both condenser and evaporator must have two refrigerant circuits that are approximately 1/3-2/3.

6. Evaporative coil must have freeze protection.

Line Length NOTES:

1) MAXIMUM LIFT IS 45 FEET (13.7M).
2) MAXIMUM EQUIVALENT LENGTH

OF EACH STANDARD LINE IS 60 FEET

(18.3M); SEE PARAGRAPH 6,

MECHANICAL.
3) CAUTION: MAXIMUM EQUIVALENT

LENGTH OF AN OPTIONAL HOT GAS

BYPASS LINE IS 30 FT (9.1M).

DISCONNECT

SWITCH *

OPTIONAL “A” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

OPTIONAL “B” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

“B” CIRCUIT

SUCTION LINE
“B” CIRCUIT

LIQUID LINE

24V CONTROL

WIRE

DISCONNECT SWITCH *

“A” CIRCUIT

SUCTION LINE

“A” CIRCUIT

LIQUID LINE

LIQUID LINE

FILTER DRIER
LIQUID LINE

FILTER DRIER

OPTIONAL “B” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

OPTIONAL “A” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

POWER

LINE

LIQUID LINE

SOLENOID VALVE **

TWO-CIRCUIT (1/3-2/3)

CONDENSING UNIT

FOR R-410A

REFRIGERANT

GROUND

(PAD)

LEGEND

NEC - National Electric Code

TXV - Thermostatic Expansion Valve

- Piping