Condensing unit installed on the roof – Reznor MASA Unit Installation Manual User Manual

Page 9

Advertising
background image

Form I-COND, P/N 220746R6, Page 9

FIGURE 4A - Refrigerant Piping on a PreevA® Split System with the Condensing Unit

Installed at a Higher Level than the Air Handler Unit

*Field-supplied per NEC.

**Field-supplied

SIGHT GLASS/

MOISTURE

INDICATOR **

CONDENSING UNIT INSTALLED ON THE ROOF

TO

CONDENSING

UNIT

FROM

AIR

HANDLER

Line Length NOTES:
1) MAXIMUM LIFT IS

45 FEET (13.7M).
2) MAXIMUM EQUIVALENT

LENGTH OF EACH

STANDARD LINE IS 60 FEET

(18.3M); SEE PARAGRAPH 6,

MECHANICAL.
3) CAUTION: MAXIMUM

EQUIVALENT LENGTH

OF AN OPTIONAL HOT GAS

BYPASS LINE IS 30 FT (9.1M).

TWO-CIRCUIT (1/3-2/3)

CONDENSING

UNIT FOR R-410A

REFRIGERANT

AIR HANDLER

UNIT WITH A

TWO-CIRCUIT (1/3-2/3)

COOLING COIL

FOR R-410A

REFRIGERANT

NOTES:

1. All piping must follow standard piping techniques for R-410A refrigerant. Refer to ASHRAE Guide and

ASME Informational Standards for piping information. Comply with CSA Mechanical Refrigeration Code

CSA B52, ASHRAE Guide Section 15, all municipal codes, and state or provincial requirements.

2. All wiring must comply with all applicable local and national codes.

3. Wiring and piping shown are general points-of-connection guides only and are not intended to apply

to or include all details for a specific installation. Refer to ASHRAE Guide Section 15 for piping details.

4. Internal factory-supplied TXV’s on PREEVA air handler unit are not shown. (Air handler must have

properly sized thermal expansion valves.)

5. Both condenser and evaporator must have two refrigerant circuits that are approximately 1/3-2/3.

6. Evaporative coil must have freeze protection.

ROOF

OPTIONAL “B” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

OPTIONAL “A” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

DISCONNECT

SWITCH *

DISCONNECT

SWITCH *

LIQUID LINE

FILTER DRIER

LIQUID LINE

FILTER DRIER

POWER

WIRE

“B” CIRCUIT

LIQUID LINE

24V CONTROL

WIRE

“A” CIRCUIT

LIQUID LINE

OPTIONAL “A” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

OPTIONAL “B” CIRCUIT HOT GAS

BYPASS (See Line Length NOTE 3)

“A” CIRCUIT

SUCTION LINE

“B” CIRCUIT

SUCTION LINE

LIQUID LINE

SOLENOID

VALVE **

LEGEND

NEC - National Electric Code

TXV - Thermostatic Expansion

Valve

Piping