0 electrical and wiring, 1 general, 1 wiring diagram – Reznor MASA Unit Installation Manual User Manual

Page 18: 2 supply wiring, 1 disconnect switch 7.2.2 supply voltage, Warning, Caution

Advertising
background image

Form I-COND, P/N 220746R6, Page 18

If there is no dip tube, verify that the refrigerant is R-410A and turn the cylinder

upside down.

WARNING

Do not release refrigerant to the atmosphere. When adding

or removing refrigerant, the qualified technician must comply

with all national, state/province, and local laws. See Hazard

Levels, page 3.

Long Line Sets/High Refrigerant Charge

If the system charge is larger than 20 lbs, the compressor manufacturer recom-

mends adding one fluid ounce (28ml) of oil for every 5 pounds of refrigerant

over 20. Use *Copeland Ultra 22 CC POE oil.
If because of long line length, the amount of refrigerant charged exceeds the

capacity of both the condenser and the receiver, the excess refrigerant will

need to be reclaimed during pumpdown. Follow industry standard procedures

for reclaiming. Do not release refrigerant to the atmosphere.

7.2 Supply Wiring

7.0 Electrical and

Wiring

7.1 General

All electrical wiring and connections including electrical grounding must be

made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest

edition) or, in Canada, the Canadian Electrical Code, Part I-C.S.A. Standard

C22.l. Check any local ordinances or utility company requirements that apply.

Check the rating plate on the condensing unit for the supply voltage and the

current requirements. A separate line voltage supply with overcurrent protec-

tion should be run directly from the main electrical panel to the unit making

connections in the electrical compartment. See

FIGURE 2, page 6, for electri-

cal supply and control entrance locations.

6.4 R-410A

Refrigerant

Charge (cont’d)

6.0 Mechanical

(cont’d)

7.1.1 Wiring Diagram

Each unit has a wiring diagram in the electrical compartment.

FIGURE 6, page

21, is a typical wiring diagram.

7.2.1 Disconnect Switch

A field-supplied disconnect switch is required. When installing the disconnect

switch, be careful that the conduit and switch housing are clear of all ser-

vice doors. See suggested location in

FIGURE 2, page 6. If disconnect is not

mounted on the cabinet, comply with local requirements allowing at least three

feet (1M) of service room between the disconnect switch and any service pan-

els. When providing or replacing fuses in a fusible disconnect switch, use dual

element time delay fuses and size 1.25 times the maximum total input amps.

7.2.2 Supply Voltage

The electric supply to the unit must meet stringent requirements for the system

to operate properly. Voltage supply should be within ±10% or as stated on the

rating plate. Maximum imbalance on a 3-phase system is 2%. Follow instruc-

tions below to check.

CAUTION

If this condensing unit is allowed to operate on an electric

supply that is not within the specified tolerances, the product

warranty shall be void. See Hazard Levels, page 3.

Advertising