3 other compressor and refrigerant, Controls, Cug2 or cug3) – Reznor MASA Unit Installation Manual User Manual

Page 22: Caution, 0 controls and operation (cont’d)

Advertising
background image

Form I-COND, P/N 220746R6, Page 22

8.3 Other Compressor and Refrigerant Controls

Check the wiring diagram on the unit to determine if it has optional controls.

8.3.1 High Pressure Cutoff

The high pressure cutoff control is located in the discharge line as it exits the

compressor. If the discharge pressure exceeds the high pressure cutoff setting

(600±15psi), the control will stop compressor and condenser fan operation.

The high pressure cutoff control is a manual reset device. It can be reset when

the pressure drops below the differential setting (400 ±15psi). Correct the prob-

lem before resetting the device to restart operation of the system.

8.3.2 Low Pressure Cutoff

The low pressure cutoff control is located in the suction line as it enters the

compressor. If the suction pressure drops below the low pressure cutoff setting

(35±5psi), the control will stop compressor and condenser fan operation. The

low pressure cutoff control will automatically restart operation when the suction

pressure goes above 50±5psi.

8.3.3 Hot Gas Bypass Valve (Option CUG2 or CUG3)

If ordered with Option CUG 2 or 3, the bypass valve will provide expanded

compressor modulation at low outside air temperatures by allowing some of

the gas from the discharge line to be re-routed directly to the evaporator coil.

Option CUG2 has a hot gas bypass on one circuit. Option CUG3 has a hot gas

bypass on both circuits.
The hot gas bypass valve is factory set. However, the factory setting should

be checked at startup. To check the valve operation and/or make field adjust-

ments, it is necessary to simulate a light load condition as described below.
Check Hot Gas Bypass Valve Setting - Connect a pressure gauge to the suc-

tion line and block the entering air to the evaporator coil. Suction pressure will

drop, and the hot gas bypass valve should begin to open at approximately 115

psi and will be fully open at 95 psi. When the valve begins to open, it will be hot

to the touch (see caution below).

CAUTION

Touching the operating hot gas bypass valve can cause a

burn. Use caution when checking and adjusting the valve.

See Hazard Levels, page 3.

If pressure needs to be adjusted, remove the cap and turn the adjusting stem

clockwise to increase the pressure setting or counterclockwise to decrease the

pressure setting. Make adjustments in small increments. Allow five minutes

between adjustments for the system to stabilize. When finished, replace the

cap on the adjustment stem and remove the pressure gauge.

8.3.4 Compressor Protection (Option CUB1)

If ordered with Option CUB1, the condensing unit has a five-minute anti-short

cycle timer on compressor operation.
NOTE: Standard with Reznor PreevA

®

with digital FX05 controls.

8.3.5 Crankcase Heaters

Each scroll compressor in the condensing unit has a band-type crankcase

heater. Crankcase heaters must always have been energized for at least 24

hours prior to operating the compressor.

8.0 Controls and

Operation

(cont’d)

Advertising