background image

Form I-COND, P/N 220746R6, Page 21

TABLE 8 - 24V

Control Wiring Size

and Length

24V Field Control Wiring Length/Gauge

Total Wire Length

Distance from Unit to Control

Minimum Wire Gauge

150ft (46M)

75ft (23M)

18

250ft (76M)

125ft (38M)

16

350ft (107M)

175ft (53M)

14

7.4 Control Wiring

The condensing unit is equipped with a low voltage (24V) control circuit.

Depending on the air handler controls, the control system is either analog or

digital.
24V wires enter the cabinet just below the line voltage entrance and must be

routed over to the low voltage compartment on the left. (See

FIGURE 8, page

28.) Connections are made at the low voltage terminal blocks.
See

TABLE 8 for wiring size and length requirements.

FIGURE 7A - Analog

Control Connection

Wiring Diagram

WIRING CODE
BROWN - BR

RED - R

ORANGE - O

PURPLE - PR

TERMINAL BLOCK -- LOW VOLTAGE

COMPARTMENT

UNIT

TERMINALS

7

8

X

Y1

Y2

Y3

FACTORY WIRING

FIELD WIRING

Y3

Y1

Y2

PR

O

R

T7350D THERMOST

AT

CUST

OMER'S

X

Y2

Y3

Y1

PR

8

O

R

8

8

X

2ND STAGE

RELAY COIL (CR2)

1ST STAGE

RELAY COIL (CR1)

3RD STAGE

RELAY COIL (CR3)

BR

7

CR

X

BR

BR

7

7

CR

CR

X

X

8.0 Controls and

Operation

Make control connections at the 24V terminal blocks in the low voltage elec-

trical compartment. See analog control connections in

FIGURE 7A or digital

control connections in

FIGURE 7B.

8.1 Analog Control

System

If using an analog control system, connection is to a low-voltage (24V) 3-stage

thermostat. The thermostat may be field-provided or an accessory to the air

handling unit.

8.2 Digital Control

System

If connecting to a PreevA

®

digital control system, control is from an

FX05 programmable controller located in the control compartment of the

PreevA

®

air handler (Reznor

®

Model SDH, PDH, or RDH). Refer to the Pre-

evA

®

installation manual (either Form I-PDH/SDH or Form I-RDH) for com-

plete control information.

PREEVA UNIT

(WITH FX-05 CONTROLLER)

CUSTOMER'S

63

61

62

87

Y3

Y1

Y2

PR

O

R

8

8

8

BR

7

CR

X

BR

BR

7

7

CR

CR

X

X

X

TERMINAL BLOCK -- LOW VOLTAGE

COMPARTMENT

UNIT

TERMINALS

7

8

X

Y1

Y2

Y3

FACTORY WIRING

FIELD WIRING

WIRING CODE
BROWN - BR

RED - R

ORANGE - O

PURPLE - PR

2ND STAGE

RELAY COIL (CR2)

1ST STAGE

RELAY COIL (CR1)

3RD STAGE

RELAY COIL (CR3)

FIGURE 7B - Digital