Caution, Warning – Reznor MASA Unit Installation Manual User Manual

Page 33

Advertising
background image

Form I-COND, P/N 220746R6, Page 33

CAUTION

Crankcase heaters must be allowed to warm up for at least

24 hours prior to startup. Disable cooling controls before

turning on power to warmup crankcase heaters. See Hazard

Levels, page 3.

Step 9. Charge the System (R-410A refrigerant)

Charge the circuit according to the information in Paragraph 6.4. R-410A

refrigerant must be charged as a LIQUID.

Step 10 . System Startup

Connect refrigerant pressure gauges and electric meters. Refer to Start-Up

Paragraph 9.2 and perform all procedures required prior to checking sub-

cooling and superheat which is done in

Step 11.

CAUTION

Be sure to connect pressure gauges to the suction and

discharge lines before start-up so that compressor rotation

can be checked immediately. Scroll compressors will be

destroyed if allowed to operate in reverse. See Hazard Levels,

page 3.

Step 11. Check Subcooling and Superheat

Refer to Start-Up Paragraph 9.2 and follow instructions for checking sub-

cooling and superheat.

WARNING

Do not release refrigerant to the atmosphere. When adding or

removing refrigerant, the qualified technician must comply

with all national, state/province, and local laws.

Step 12. (Select the procedure that applies.)

IF the oil measured in Step 2 was significantly less than in TABLE 10

or the acid test in

Step 2 indicated a burnout, do the following:

a) Operate the unit for several hours. Check the pressure drop through the

temporary suction line filter drier. If the pressure drop exceeds 8 psig,

recover the refrigerant, replace the suction line filter drier with the same

type as removed, replace the liquid line filter drier, evacuate the circuit,

and re-charge with the recovered refrigerant (see Paragraph 6.4).

Continue to monitor the pressure drop through the suction line filter drier

and repeat the process above until the pressure does not exceed 8 psig

after several hours of operation. (NOTE: System must be allowed to run

no more than 72 hours with a suction line filter drier.)

b) Allow the system to operate for 4-8 hours. Recover the refrigerant and

take an oil sample. Retest the oil for acid.

c) If the test for acid is negative, remove the suction line filter drier, replace

the liquid line drier, evacuate, and re-charge the system with the recov-

ered refrigerant.

If the test indicates acid, replace both the liquid line filter drier and the

suction line filter drier and repeat b) and c).

Advertising