9.2.3 Refrigerant

Charge

IMPORTANT

All refrigeration

checks MUST

be made by a

refrigeration

technician

qualified in

R-410A refrigerant.

Equipment and

tools MUST be

designed for

R-410A refrigerant.

PREPARATION:

To verify superheat and subcooling, outdoor temperature must be

between 70-95°F (21-35°C). If temperature is not within this range,

consult the factory service department before charging.

Operate for 30 minutes for system to stabilize.

Check BOTH refrigerant circuit A and circuit B; isolate each cir-

cuit before measuring superheat and subcooling.

If the circuit has an optional hot gas bypass valve, disable it

before measuring superheat and subcooling. To disable, remove

cap and backoff spring tension. Be sure to reset after checking (See

Paragraphs 8.3.3 and 9.2.4).

9.2.3.1 Check SUBCOOLING

Measure and record temperature and pressure of the liquid line at

the condenser coil outlet.

STEP 1) Record Measurements: Temperature =

________°F (°C) and Pressure = ________ psig

STEP 2) From Temperature/Pressure Conversion Chart,

APPENDIX, page 40, convert Measured Pressure (STEP
1) to ________°F (°C)

STEP 3) Subtract Measured Temperature (STEP 1) from

Temperature from Conversion Chart (STEP 2)
________°F (°C) - ________°F (°C) = ________°F (°C)
degrees of Subcooling

Recommended subcooling with outdoor temperature range of

70-95°F (21-35°C) is 14-18°F (7.8-10°C).

Too much subcooling indicates a refrigerant overcharge. To reduce

the subcooling, remove excess refrigerant. Too little subcooling indi-

cates a refrigerant undercharge. To increase subcooling, slowly add

R-410A refrigerant.

WARNING

Do not release refrigerant to the atmosphere. When adding

or removing refrigerant, the qualified technician must

comply with all national, state/province, and local laws.

9.2.3.2 Determine SUPERHEAT

Measure and record temperature (insulate probe from surrounding air tem-

perature) and pressure in the suction line at the compressor inlet.

STEP 1) Record Measurements: Temperature =

_______°F (°C) and Pressure = _______ psig