Form I-COND, P/N 220746R6, Page 8

FIGURE 3 - Condensing

Unit Refrigerant Piping

Connection Locations

6.1.2 Location of Piping Connections at the Split System

Evaporator Coil

It is important to identify the Circuit A and Circuit B connections at the evapora-

tor coil before running the refrigerant lines.
Circuit A on the condenser (

FIGURE 3) is the smaller (33%) circuit and should

be connected to the 33% circuit of the evaporator coil. Circuit B on the con-

denser (

FIGURE 3) is the larger (67%) circuit and should be connected to the

67% circuit of the evaporator coil.
On the evaporator coil, identify the liquid line connection at the distributor for

the smaller circuit (Circuit A). Force nitrogen into the Circuit A connection and

check which suction line connection corresponds to it. If the suction line con-

nection is not identified, mark it as Circuit A. For verification, repeat the pro-

cess with the larger circuit and mark the suction line connection as Circuit B.
Refer to

FIGURE 4A or 4B for illustration of a split system refrigerant piping

system connecting a MASA condensing unit to a PreevA

®

evaporator coil. In

FIGURE 4A, the condensing unit is higher than the evaporator coil. In FIGURE

4B, the condensing unit is lower than the evaporator coil.

6.0 Mechanical

(cont’d)

Circuit A (1/3 circuit)

Piping Entrance Holes -

Liquid line on the left;

Suction line on the right

Electrical and

Compressor

Compartment

Access

Panel

Circuit B (2/3 circuit)

Piping Entrance Holes -

Liquid line on the left;

Suction line on the right

Entrances for Optional

Hot Gas Bypass Connections

Left - Circuit A;

Right - Circuit B

R-410A Compressors

(identified by

Circuit A & B)

B

A

Electrical

Compartment

6.1.1 Location of Piping Connections at the Condensing Unit

(cont’d)