Form I-COND, P/N 220746R6, Page 20

FIGURE 6 - Typical Condensing Unit Wiring Diagram

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

5

6

4

3

2

30

FIELD CONTROL WIRING

350 FEET #14 GA.

250 FEET #16 GA.

150 FEET #18 GA.

LENGTH WIRE SIZE

TOTAL WIRE MINIMUM RECOMMENDED

MASA UNIT

TERMINALS

TERMINAL BLOCK -- LOW VOLTAGE

TERMINAL BLOCK -- HIGH VOLTAGE
COMPARTMENT

COMPARTMENT

R

T3

L3

R

C

A

BK

CONTACTOR

B

T2

L2

Y

L1

T1

Y

BK

COMPRESSOR

"B" COMPRESSOR

IOL

#2 CONDENSER FAN

CAPACITOR

W

BK

IOL

W

R

1

#1

G

GRD

W

A

B

L3

T3

Y

L2

T2

W

IOL

CONTACTOR CONTACTS

CONDENSER

BK

L1

T1

BK

CONDENSER FAN

CAPACITOR

R

GRD

G

"A" COMPRESSOR

B

A

C

L3

R

T3

CONTACTOR

L2

Y

T2

L1

BK

T1

R

IOL

Y

BK

COMPRESSOR

(CF2)

(CF1)

208-240-480/3/60

DISCONNECT SWITCH

OPTIONAL FUSIBLE

8

BK

BK

C

C

NO

BK

NC

BK

LPCO

LPCO

CONDENSER

RELAY CONTACTS

FAN PERM.

4

4

Y

2

PR

BK

O

6

C

C

NO

BK

HPCO

HPCO

NC

2ND STAGE COMPRESSOR
CONTACTOR COIL

PERM. RELAY COIL (CR4)

CONDENSER FAN

CR

26

CR

30

8

BK

7

BR

6 - 7 - 8

24 - 25

2

CONTACTOR COIL

1ST STAGE COMPRESSOR

CONTACTOR COIL
11 - 12 - 13

20

CR

24

CR

O

BL

BR

BR

BR

CONDENSER

1 - 2 - 3

2

A

C

CONTROL

TRANSFORMER

BREAKER

CIRCUIT

Y/W

24 V

BK

(SEE TRANSFORMER NOTES)

75 VA

Y

2

1

4

8

#1 CR

ANK

CASE

HEA

TER

BK

BK

R

7

8

CR

33

20

BR

X

RELAY COIL (CR1)

1ST STAGE

O

34
CR

8

7

RELAY COIL (CR2)

2ND STAGE

24 - 26

X

BR

GRD

GRD

Y

BR

A
B
C

O

R

GR

WIRING CODE

BLACK - BK
BROWN - BR
RED - R
ORANGE - O
YELLOW - Y
GREEN - GR
BLUE - BL
PURPLE - PR
WHITE - W

GRAY - GY
YELLOW/WHITE - Y/W

CONTACTS

CONTACTS

HEA

TER

#2 CR

ANK

CASE

BK

BK

GR

1ST STAGE

2ND STAGE

M SERIES - AK5, 6 or 7-CUB1 DWG. #229701 REV. #5

LINE V

1

1

5

7

9

BL

BL

BL

BL

PR

RELAY COIL (CR3)

PR

X

8

CR

35

BR

7

3RD STAGE

20

X

Y1

Y2

Y3

63

62

61

87

CUSTOMER'S PREEVA UNIT

1
2
3
4
5

7
8
9

X
Y1
Y2
Y3

1

SAFETY

#2 ICM 221

Y

T1

SAFETY

T

C

#1 ICM 221

Y

SAFETY

SAFETY

T1

C

T

BK

BK

2ND STAGE

RELAY CONTACTS

RELAY CONTACTS

2ND STAGE

Y

4

Y

5

6

W

1

PR

3RD STAGE

RELAY CONTACTS

Y

4

6

W

1ST STAGE

RELAY CONTACTS

6

3

3

PR

4

W

PR

TRANSFORMER NOTES

FOR 208 VOLTS - USE BLACK AND RED LEADS
FOR 240 VOLTS - USE BLACK AND ORANGE LEADS
FOR 480 VOLTS - USE BLACK AND GRAY LEADS

BR

BR

OPTIONAL FACTORY WIRING

FACTORY WIRING

FIELD WIRING

(SEE NOTE #1)

X

CR

27

LOCKOUT INDICATION
RELAY COIL

CUSTOMER'S #2

2

X

21

CR

CUSTOMER'S #1

RELAY COIL

LOCKOUT INDICATION

2

(WITH FX05 CONTROLLER)

Y1

Y3

T7350D THERMOST

AT

(SEE NO

TE #2)

X

Y2

X

CUST

OMER'S

OPERATING SEQUENCE

1. FOR A TWO STAGE COOLING SEQUENCE JUMPER Y2 TO Y3.

THE SEQUENCE IS #1 THEN #1 AND #2.

2. FOR A THREE STAGE COOLING SEQUENCE, THE SEQUENCE

IS #1 THEN #2 THEN #1 AND #2.

3. WHEN THE ANTI-SHORT CYCLE PROTECTION MODULE IS IN

A LOCKOUT CONDITION, THE LOCKOUT INDICATION RELAY

COIL IS ENERGIZED.

AND IS WIRED IN SERIES WITH OPTIONAL FROSTSTATS WHEN APPLICABLE.

2. THERMOSTAT IS WIRED AND POWERED PER MANUFACTURER'S LITERATURE

1. #2 CONDENSER FAN ON SIZE 120 THRU 180 UNITS ONLY.

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25

4. USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.
5. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

6. DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS

TIMES THE MAXIMUM TOTAL INPUT AMPS.

AN OPTION.

NOTES

3. SEE RATING PLATE LABEL FOR MCA, TO DETERMINE LINE FEED COPPER WIRE SIZE.

7. USE COPPER CONDUCTORS ONLY.

X

Y1

Y2

Y3

49

47

7

(WITHOUT FX05 CONTROLLER)

Y1

Y3

T7350D THERMOST

AT

(SEE NO

TE #2)

X

Y2

X

CUST

OMER'S

48

46

TO PREEVA UNIT

SEE SHEET #2

TO PREEVA UNIT

SEE SHEET #2

CUSTOMER'S PREEVA UNIT

ALTERNATE WIRING

K

250V. - 8 FLA / 48 LRA

2

4

#14 GA BL

125V. - 12 FLA / 60 LRA

INTERFACE NOT TO EXCEED

FOR CUSTOMER'S

RELAY CONTACTS

#14 GA BK

#14 GA Y

6

L

M

"B" CIRCUIT SOLENOID VALVE

G

250V. - 8 FLA / 48 LRA

2

4

#14 GA BL

125V. - 12 FLA / 60 LRA

INTERFACE NOT TO EXCEED

FOR CUSTOMER'S

RELAY CONTACTS

#14 GA BK

#14 GA Y

6

H

J

"A" CIRCUIT SOLENOID VALVE

K
L
M

G
H
J

12

13

14

15

19
CR

BL

12

13

RELAY COIL

"A" CIRCUIT SOLENOID VALVE

12 - 13

8

7

12
13
14
15

BR

BR

25
CR

BK

14

RELAY COIL

"B" CIRCUIT SOLENOID VALVE

12 - 13

8

7

BR

15

BR

7.0 Electrical and Wiring (cont’d)