10.2 Maintenance

Schedule

Beginning of the cooling season or more frequently in year-

round cooling climate:

Inspect the wiring for any damaged wire. Replace damaged wiring.

Inspect the condenser fan. Clean as needed. See Paragraph 10.3.

Inspect/clean condenser coil. See Paragraph 10.4.

Check compressor operation. See Paragraph 10.5.

Check refrigerant pressure and temperatures (both superheat and

subcool). These measurements must be taken when the system is in

operation. See Paragraph 10.5.

FIGURE 8 -

Electrical

Compartment

showing

Control

Locations

Electrical and

Compressor

Compartment

Access

Panel

Top (removed for clarity)

Relays

Capacitor

Transformer

Line Voltage

Terminal Block

24V Terminal Block

Line Voltage

Entrance

Control Voltage

Entrance

Contactors

R-410A Compressors

(identified by

Circuit A & B)

B

A

10.3 Condenser

Fan(s)

Maintenance

NOTE: If replacement

parts are required, use

only factory-authorized

parts. For information,

go to www.RezSpec.

com. or call 1-800-695-

1901.

Check condenser fans. Carefully clean debris and dirt from guards, fan blades

and motors. If any parts need to be replaced, use only factory-authorized

replacement parts.

Fan rotation is

counterclockwise.

Top View

Torque blade

setscrew to

120 in/lbs ±2.

Side View

1 to 1-1/2 inches (25-38mm) maximum

distance from top of fan blade down

to top edge of fan orifice in cabinet top

Motor

Condenser Top

Fan Blade

FIGURE 9 -

Condenser

Fan Rotation

and Fan

Blade

Spacing from

Top Edge of

Fan Orifice