Echelon Lumewave CRD 3000 Street Light Bridge User Manual

Page 116

Advertising
background image

106

Interoperable Interface for the Street Light Bridge

Variable

Description

Ok to Modify?

nciPriRpt

Defines the repeat count for the

primary path.

Yes
See Defining the Networking

Channels on page 36 for

information about defining

channels.

nciSecChs

Defines channels for RF data

transmission on the secondary

(alternate) LonTalk (ISO/IEC

14908-3) path.
Valid values are 11 to 26. Values

outside this range are ignored.

Yes
See Defining the Networking

Channels on page 36 for

information about defining

channels.
Use 0 (zero) to indicate an unused

channel.

nciSecRpt

Contains the repeat count used for

the secondary path.

Yes
See Defining the Networking

Channels on page 36 for

information about defining

channels.

nciRepeatMode

Defines the Street Light Bridge

repeating type:
0 – normal repeating operation

(PL and RF)
1 – PL-PL repeating (no RF

transmission)
2 – RF-RF repeating (no PL

transmission)

Yes
See Defining Repeating on page 40

for information about setting the

repeat mode.

nciMediaAccess

Defines the power line media

access protocol:
0 – Default (media access protocol

is enabled during manufacturing,

based on the module model type)
1 – Normal (overrides firmware

setting and defines a PL-20N

channel)
2 – CENELEC (overrides firmware

setting and defines a PL-20C

channel)

Yes
See Defining the Media Access

Protocol on page 37 for information

about setting the media access

protocol.
Changes to this value take effect

only after a device resets.

Advertising