Adjusting capacitor power – CIRCUTOR computer PLUS-TF Series User Manual

Page 38

Advertising
background image

38

You can browse any parameter to see how it is programmed. However, when you attempt to edit a field,
a screen will ask for the password (Fig.44). Follow the instructions described in section 7.1 to enter the
password.

If the unit is in operation, the screen shown on Fig. 45 will appear before the setup process is carried out
and the regulator will disconnect any steps connected.

Fig.44.- Password request

Fig. 45.- Setup with connected steps.

The indispensable parameters that must be configured to start-up the Computer plus are:

C Power kvar

Capacitor

V-I Connections

Transf. Ratio

Compensation

Target Cos

φ

tact, trec

Apart from the indispensable parameters shown on the previous list, Computer plus has a series of
optional parameters that do not have a direct impact on the compensation process. These parameters
are:

Date/Time

Display

Communications

Clear/Update


7.3.3

Adjusting Capacitor Power

This unit can be used to adjust the power of each capacitor step in the compensation unit.

The adjustment method is described in section 7.2.1 for the Plug&Play settings.