Electrical data – BECKHOFF BK3000 User Manual
Page 14

Basic information
14
BK3xxx/LC3100
Electrical data
The Profibus couplers differ by virtue of their capacity levels and maximum
baud rates. The BK30xx variants are capable of supporting up to 1.5
MBaud and the LC3100 and BK31xx series support up to 12 Mbaud. The
electrical data specific to the fieldbus is given in this chapter. The following
data distinguishes between a standard and an economy variant (BK3x00
and BK3x10) and an low cost variant (LC3100). Compatability with the
Profibus is guaranteed in any case. Contrary to the standard bus coupler,
the economy variant is limited of the number of I/O´s. Thus, there is no
possibility of connecting inputs and outputs other than digital ones. The
following table lists an overview of all data:
Technical Data
BK3000
BK3010
BK3100
BK3110
BK3500
LC3100
Supply voltage
24 V DC
Input current
70mA +
(total K bus
current)/4,
500 mA max.
80mA +
(total K bus
current)/4,
200 mA max.
70mA +
(total K bus
current)/4,
500 mA max.
80mA +
(total K bus
current)/4,
200 mA max.
80mA +
(total K bus
current)/4,
500 mA max.
60mA +
(total K bus
current)/4,
200 mA max.
Power-on surge
2.5 x steady operating current
K bus supply
current up to
1750
mA
max.
500 mA max. 1750 mA
max.
500 mA max. 1750 mA
max.
500 mA max.
Configuration
facility
via KS2000 or the controller
Number of bus
terminals
64
Digital
peripheral signals
256 inputs/outputs
Analogue peripheral
signals
128
inputs/output
s
---
128
inputs/outputs
---
128
inputs/output
s
---
Peripheral bytes
244 bytes I /
244 bytes O
32 bytes I /
32 bytes O
64 bytes I /
64 bytes O
DP only
128 bytes I /
128 bytes O
32 bytes I /
32 bytes O
128 bytes I /
128 bytes O
32 bytes I /
32 bytes O
Baud rate
1.5 Mbaud
1.5 Mbaud
12 Mbaud
12 Mbaud
1.5 Mbaud
12 Mbaud
Protocol
DP
FMS
DP
DPV1
DP
FMS
DP
DPV1
DP
DPV1
DP
DPV1
Bus connection
D-sub
9-pin
D-sub
9-pin
D-sub
9-pin
D-sub
9-pin
2
x
HP
Simplex plug
Directly to the
spring-loaded
terminals
Voltage of the
power contact
24 V DC / AC max.
Power contacts
current drawn
10 A max.
Electric strength
500 Veff (power contact / supply voltage / fieldbus)
none
Typical weight
170 g
150 g
170 g
150 g
170 g
75 g
Operating
temperature
0°C ... +55°C
Storage
temperature
-20°C ... +85°C
Relative humidity
95% without dew formation
Vibration/
shock stability
according to IEC 68-2-6 / IEC 68-2-27
EMC
immunity/transmissi
on
according to EN 50082 (ESD, burst) / EN 50081
Installation location arbitrary
Protection class
IP20