Terminal bus error – BECKHOFF BK3000 User Manual

Page 19

Advertising
background image

Basic information

BK3xxx/LC3100

19


Terminal bus error

Error code

Error code
argument

Description

Remedy

Persistent,
continuous
blinking

EMC problems

- Check power supply for overvoltage or
undervoltage peaks
- Implement EMC measures
- If a K-bus error is present, it can be
localised by a restart of the coupler (by
switching it off and then on again)

1 pulse

0

1


2

EEPROM checksum error

Inline code buffer overflow


Unknown data type

- Set manufacturer’s setting with the
KS2000
- Connect fewer terminals; too many
entries in the table for the programmed
configuration
- Software update required for the coupler

2 pulses

0


n (n > 0)

Programmed configuration
Incorrect table entry / bus
coupler
Incorrect table comparison
(terminal n)

- Check programmed configuration for
correctness

- Incorrect table entry / bus coupler

3 pulses

0

Terminal bus command error

- No terminal connected; attach terminals.
- One of the terminals is defective; halve
the number of terminals attached and
check whether the error is still present with
the remaining terminals. Repeat until the
defective terminal is located.

4 pulses

0

n

Terminal bus data error

Break behind terminal n (0:
coupler)0

n

- Check whether the n+1 terminal is
correctly connected; replace if necessary.
– Check whether the end terminal 9010 is
connected.

5 pulses

n

Terminal bus error with register
communication with terminal n

Replace terminal n.

7 pulses
(BK3010,
BK3110, LC3100
only)

n

Analogue terminal inserted
n

th

terminal is an analogue

terminal

Remove n

th

terminal and switch the

coupler off and then on again.



Profibus configuration data errors: BK3000/BK3100

I/O-Err

Remedy

6 pulses

0
n (n>0)

Not enough DP-Cfg data received.
Faulty DP-Cfg data byte.

Check DP configuration.

8 pulses

0
n (n>0)

Not enough User-Prm data received
Faulty User-Prm data byte

Check DP user parameters.



Profibus configuration data errors:
BK3010/BK3110/BK3500

DIA

Remedy

1 pulse

0
n (n>0)

Not enough DP-Cfg data received.
Faulty DP-Cfg data byte.

Check DP configuration.

2 pulses

0
n (n>0)

Not enough User-Prm data received
Faulty User-Prm data byte

Check DP user parameters.